Comments On Electrical Data Notes - Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS

5.15 - Comments on electrical data notes

• 30RB/30RBP units have a single power connection point located immediately
upstream of the main switch.
• 30RQ/30RQP units from 165R to 520R have a single power connection point
located immediately upstream of the main disconnect switch.
• 30RQP units from 620R to 1040R have two connection points located immediately
upstream of the main disconnect switch for each module.
• The control box includes:
- A main disconnect switch,
- The motor start-up and protection devices for each compressor, the fans and
the pumps,
- The control devices.
• Field connections:
All connections to the system and the electrical installations must be in accordance
with all applicable codes.
• 30RB/30RBP 30RQ/30RQP units are designed and built to ensure conformance
with these codes. The recommendations of European standard EN 60204-1
(corresponding to IEC 60204-1) (Machine safety - Electrical machine components 
- part 1: General regulations) are specifically taken into account, when designing 
the electrical equipment.
Notes
• Generally the recommendations of IEC 60364 are accepted as compliance with
the requirements of the installation regulation.
• Compliance with EN 60204-1 is the best means of ensuring compliance with the
requirements (§1.5.1) of the Machinery Directive.
• Annex B of standard EN 60204-1 specifies the electrical features used for the 
operation of the units.
• Operating conditions of 30RB/30RBP 30RQ/30RQP units are described below:
1. Environment
(1)
  The classification of the environment is specified in standard EN 60364:
- Outdoor installation
,
(1)
- Ambient temperature range: Minimum temperature -20 °C to +48 °C,
- Altitude: AC1 of 2000 m or less (for the hydraulic module, see the paragraph 
"Electrical data for the hydraulic module"),
- Presence of solid foreign bodies: Class AE3 (no significant dust present)
- Presence of corrosive and polluting substances, class AF1 (negligible),
- Competence of personnel: BA4 (trained personnel).
2. Compatibility for low-frequency conducted disturbances at class 2 levels as
per the IEC 61000-2-4 standard:
- Power supply frequency variation: +- 2Hz
- Phase imbalance: 2%
- Total Voltage Harmonic Distortion (THDV): 8%
3. The neutral (N) wire must not be connected directly to the unit (if necessary 
use a transformer).
4. Overcurrent protection of the power supply conductors is not provided with
the unit.
5. The  factory-fitted  disconnect  switch(es)/circuit  breaker(s)  are  of  a  type 
suitable for power interruption in accordance with EN 60947-3 (corresponds 
to IEC 60947-3).
6. The  units  are  designed  for  connection  to  TN  type  networks  (IEC  60364). 
In IT networks, if noise filters are integrated into the variable frequency drive(s), 
this will render the units unsuitable for their intended purpose. In addition,
the equipment characteristics in case of insulation failure are modified. Provide 
a local earth; consult competent local organisations to complete the electrical
installation.
Machines 30RB/30RBP 30RQ/30RQP are designed for use in domestic /
residential and industrial environments:
Machines that are not equipped with variable speed drives comply with general
standards.
- 61000-6-3: General standards - Standard emission for residential,
commercial and light industry,
- 61000-6-2: General standards - Immunity for industrial environments
Machines  equipped  with  one  or  more  variable  frequency  drives  (RBP 
RQP,  options:  28,  116V,  116W)  comply  with  standard  EN61800  -  3 
"Variable-speed electrical power drive systems - Part 3: EMC requirements
and  specific  test methods"  for the following  classifications:  Use  in  first 
and second environments
- Category  C3 applicable  in the first environment,  on stationary  devices 
designed to be installed and commissioned by a professional.
Warning: In a residential environment, this product may cause radio
interference; in this case, additional mitigation measures could be required.
• Leakage currents: If protection by monitoring the leakage currents is necessary
to ensure the safety of the installation, the presence of a circuit with a
DC component as well as leakage currents introduced by the use of variable
frequency  drives  in  the  unit  must  be  considered  (RBP,  RQP,  options:  28, 
116V, 116W). In particular, a reinforced immunity protection type and/or a control 
value  not  lower  than  150  mA  are  recommended  when  selecting  differential 
protection devices.
Note: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should
,
(1)
be considered, always contact your local representative.
(1)  The required protection level for this class is IP43BW (according to reference 
document IEC 60529). As all 30RB/30RBP 30RQ/30RQP units are class IP54, 
they fulfil this protection condition.
(2)  - Example of installations included in the first environment: Commercial and 
residential buildings.
- Example of installations included in the second environment: Industrial areas,
technical facilities supplied by a specific transformer.
.
(2)
31