Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions page 88

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

12 - OPTIONS
12.2.8.2 - Free cooling operation
The unit's SmartVu
TM
control maximises the use of the
Free Cooling based on the needs of the application and the climate
conditions. Once the chilled water/ambient air temperature
differential  exceeds  the  threshold  value  by  1K,  the  SmartVu
control  activates  Free  Cooling  and  adjusts  the  air  flow  rate  to 
optimise the unit's energy performance. If the operating conditions
permit the Free Cooling to operate on its own to meet the
requirements, the compressors are stopped. Two motorised valves
direct the chilled water to the Free Cooling coils.
Operating modes:
There are three operating modes
Summer (warm weather season): Mechanical cooling mode
The liquid chiller meets the needs traditionally using the refrigerant
circuit. The fluid bypasses the Free Cooling coils and is cooled by 
the evaporator.
12.2.8.3 - General information
Corrosion protection:
With the hydraulic Free Cooling options, it is compulsory to use a glycol-based solution (EG or PG) containing corrosion inhibitors, 
in order to protect the aluminium exchangers.
It is strongly recommended that the loop is analysed each year to ensure that these inhibitors are present.
The table below gives the maximum period after which it is necessary to top up the inhibitors.
Open loop operation is prohibited.
Maximum number of years between two corrosion inhibitor top-ups:
500
1000
2500
5000
10000
15000
500
1000
Total volume in
2500
the loop* (litres)
5000
10000
15000
500
1000
2500
5000
10000
15000
* 
Also check the minimum volume in the standard "application data" section.
**
New EG or PG.
*** Volume too low.
Glycol 20%
Glycol 30%
Glycol 45%
*
See previous table.
88
Total number of Free Cooling coils connected to the water loop
2
4
6
3
2
***
6
3
2
>15
8
5
>15
>15
11
>15
>15
>15
>15
>15
>15
>15
>15
5
2
***
10
5
3
>15
12
8
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
7
4
***
14
7
5
>15
>15
12
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
>15
Volume of inhibitor to add
after x* years, as a proportion
to the total volume in the loop:
0,8%
1,2%
1,8%
Mid-season: Combination mode
It is possible to operate in combination Free Cooling and
mechanical cooling mode. This helps optimise Free Cooling
TM
operations while covering the system's cooling requirements.
The  fluid  is  pre-cooled  by  the  Free  Cooling  coils  positioned  in 
series with the refrigerant circuit evaporator which finalises cooling 
of the fluid.
Winter (cold weather season): Free Cooling mode
Depending on the capacity requested and the setpoint, all of the
requirements may be fulfilled by the Free Cooling in this operating 
mode without the fans running, thereby ensuring optimum energy
efficiency.
8
10
12
14
Glycol 20%**
***
***
***
***
2
***
***
***
4
3
3
***
8
6
5
5
>15
11
9
>15
>15
14
Glycol 30%**
***
***
***
***
2
***
***
***
6
5
4
***
10
8
7
>15
>15
14
>15
>15
>15
Glycol 45%**
***
***
***
***
4
***
***
***
9
7
6
***
>15
12
10
>15
>15
>15
>15
>15
>15
16
18
20
22
***
***
***
***
***
***
***
***
***
***
***
***
4
4
3
3
8
7
6
6
12
11
10
9
***
***
***
***
***
***
***
***
***
***
***
***
6
5
5
4
12
11
10
9
>15
>15
14
13
***
***
***
***
***
***
***
***
***
***
***
***
9
8
7
6
>15
>15
14
13
>15
>15
>15
>15
24
***
***
***
3
5
8
***
***
***
4
8
12
***
***
***
6
12
>15