8 - WATER CONNECTIONS
Figure 1: Water connections without
hydraulic module
J
I
N
Figure 2: Hydraulic connections with
hydraulic module
Example: Single-pump
F
I
K
D
G
Presence of a
stainless steel filter
Key
Components of the hydraulic module and the unit
B
Screen filter (particle size of 1.2 mm)
Expansion tank (option)
C
D
Relief valve
Circulating pump (single or dual)
E
F
Air vent
Water drain tap
G
H
Pressure sensor
Note: Provides pressure information for the pump inlet (see Control manual)
Temperature sensor
I
Note: Provides temperature information for the water exchanger outlet
(see Control manual)
J
Temperature sensor
Note: Provides temperature information for the water type heat exchanger
inlet (see Control manual)
K
Pressure sensor
Note: Provides pressure information for the water exchanger outlet (see
Control manual)
L
Check valve (if dual pump)
Plate heat exchanger
M
N
Heater or heat trace cable for frost protection (Option)
Water type heat exchanger flow rate sensor 
O
P
Water buffer tank module (Option)
F
G
J
E
H
B
Coupling for expansion
vessel (option 293)
Example: Dual-pump
F
I
K
D
G
Presence of a
stainless steel filter
Figure 3: Hydraulic connections with hydraulic
module and with water buffer tank module option
F
X
G
P
Installation components
Q
Pocket
R
Air vent
S
Flexible connection
T
Shut-off valve
U
800 µm screen filter (mandatory for a unit without a hydraulic module)
V
Pressure gauge
W
Water flow control valve
Note: Not required if hydraulic module with variable-speed pump
X
Charging valve
Y
Bypass valve for frost protection (if shut-off valves are closed (item 19) during 
winter)
Z
Buffer tank (if required)
---- Hydraulic module (unit with hydraulic module option)
Notes:
-
The installation must be protected against frost.
-
The unit's hydraulic module and the water type heat exchanger may be
protected (factory-fitted option) against frost using electric heaters and
heat trace cables (13)
-
The pressure sensors are assembled on connections without Schrader.
Depressurise and drain the system before any work.