VLT Ea4 Parallel Drive Modules
Operating Guide
All control characteristics are based on a 4-pole asynchronous motor.
7.7.12 Control Card Performance
Scan interval
7.7.13 Control Card, USB Serial Communication
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
1
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
2
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB connector on the drive or an
3
isolated USB cable/converter.
7.8 Fuses
Fuses installed on the supply side ensure that if a component breakdown (first fault) occurs inside the drive, any potential damage is
contained within the drive enclosure. For a list of fuses, see
Table 23: Fuse Options
Input voltage [V]
380–500
Danfoss A/S © 2023.01
Table
23. The drive modules are supplied with built-in AC fuses.
Type of fuse
AC fuse
DC fuse
Bussmann part number
170M7309
170M5468
AQ434333248451en-000101 / 130R1286 | 73
Specifications
5 ms
1.1 (full speed)
(1)
USB type B plug
(2)(3)