VLT Ea4 Parallel Drive Modules
Operating Guide
Troubleshooting
•
Compare the output current shown on the LCP with the drive rated current.
•
Compare the output current shown on the LCP with the measured motor current.
•
Show the thermal drive load on the LCP and monitor the value.
-
When running above the drive continuous current rating, the counter increases.
-
When running below the drive continuous current rating, the counter decreases.
6.9.12 WARNING/ALARM 10, Motor Overload Temperature
Cause
According to the electronic thermal protection (ETR), the motor is too hot.
This warning/alarm is controlled by parameter 1-90 Motor Thermal Protection:
•
If the parameter is set to warning options, the drive issues a warning or an alarm when the counter is >90%.
•
If the parameter is set to trip options, the drive trips when the counter reaches 100%.
The fault occurs when the motor runs with more than 100% overload for too long.
Troubleshooting
•
Check for motor overheating.
•
Check whether the motor is mechanically overloaded.
•
Check that the motor current set in parameter 1-24 Motor Current is correct.
•
Ensure that the motor data in parameters 1-20 to 1-25 is set correctly.
•
If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan.
•
Run AMA in parameter 1-29 Automatic Motor Adaptation (AMA). This tunes the drive to the motor more accurately and reduces
thermal loading.
6.9.13 WARNING/ALARM 11, Motor Thermistor Overtemp
Cause
The motor thermistor indicates that the motor temperature is too high.
Troubleshooting
•
Check for motor overheating.
•
Check that the thermistor is securely connected.
•
Check whether the motor is mechanically overloaded.
•
When using terminal 53 or 54:
-
Check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50
(+10 V supply).
-
Check that the terminal switch for 53 and 54 is set for voltage.
-
Check that parameter 1-93 Thermistor Resource selects 53 or 54.
•
When using terminal 18, 19, 31, 32, or 33 (digital inputs):
-
Check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and termi-
nal 50.
-
Select the terminal to use in parameter 1-93 Thermistor Resource.
6.9.14 WARNING/ALARM 12, Torque Limit
Cause
The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator
Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by
an alarm.