8.4 Ambient Conditions

Environment
IP rating
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
3)
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide.
≤ 3.7 kW (200–240 V), ≤ 7.5 kW (400–480 V)
1) Only for
≤ 3.7 kW (200–240 V), ≤ 7.5 kW (400–480 V)
2) As enclosure kit for
3) Derating for high ambient temperature, see special conditions in the Design Guide

8.5 Cable Specifications

Cable lengths and cross-sections for control cables
Max. motor cable length, shielded
Max. motor cable length, non-shielded
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1) For power cables, see electrical data tables in chapter 8.1 Electrical Data.

8.6 Control Input/Output and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
2)
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
2)
Maximum voltage on input
Pulse frequency ranges
(Duty cycle) Min. pulse width
Input resistance, R
i
MG11AK22
Instruction Manual
1)
IP00/Chassis, IP20
/Chassis, IP21
5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
1)
Danfoss A/S © 03/2015 All rights reserved.
2)
/Type 1, IP54/Type 12, IP55/Type 12, Type 3R, IP66/Type 4X
Max. 122°F [50°C] (24-hour average maximum 113°F [45°C])
-13°–+149/158°F [-25–+65/70°C]
1.0 g
class Kd
32°F [0°C]
14°F [-10°C]
3,300 ft [1,000 m]
EN 61800-3
EN 61800-3
500 ft [150 m]
1,000 ft [300 m]
1.5 mm
2
/16 AWG
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
2
0.25 mm
/24 AWG
1)
4 (6)
18, 19, 27
1)
, 29
1)
, 32, 33,
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
0–110 kHz
4.5 ms
Approx. 4 kΩ