Cable Specifications; Control Input/Output And Control Data - Danfoss VLT 380-500 V Design Manual

Parallel drive modules
Table of Contents

Advertisement

Specifications
Aggressive environment (IEC 60068-2-43) H
Aggressive gases (IEC 60721-3-3)
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
EMC standards, Emission
EMC standards, Immunity
Energy efficiency class
1) Refer to chapter 6.12 Derating Specifications for derating for high ambient temperature and derating for high altitude.
2) Determined according to EN 50598-2 at:
Rated load.
6
6
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.

6.10 Cable Specifications

Cable lengths and cross-sections for control cables
Maximum motor cable length, shielded
Maximum motor cable length, unshielded
Maximum cross-section to control terminals, flexible or rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
Maximum cross-section to 230 V terminals
Minimum cross-section to 230 V terminals
1) For power cables, see electrical data tables in chapter 6.5 Power-dependent Specifications.

6.11 Control Input/Output and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic 1 NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Minimum pulse width
Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Except Safe Torque Off input terminal 37.
Safe Torque Off (STO) Terminal 37
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
54
VLT
S test
2
1)
2)
2)
2)
i
1), 2)
(Terminal 37 is fixed PNP logic)
Danfoss A/S © 6/2016 All rights reserved.
®
Parallel Drive Modules
Maximum 45 °C (113 °F) (24-hour average maximum 40 °C (104 °F))
1)
EN 61800-4-2, EN 61800-4-3, EN 61800-4-4, EN 61800-4-5, and EN 61800-4-6
1)
Class Kd
Class 3C3
0 °C (32 °F)
-10 °C (14 °F)
-25 to +65 °C (-13 to 149 °F)
1000 m (3281 ft)
EN 61800-3
IE2
150 m (492 ft)
300 m (984 ft)
2
1.5 mm
/16 AWG
2
1 mm
/18 AWG
0.5 mm
2
/20 AWG
2
0.25 mm
/24 AWG
2
2.5 mm
/14 AWG
2
0.25 mm
/24 AWG
4 (6)
1)
18, 19, 27
1)
, 29
1)
, 32, 33
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
0–110 kHz
4.5 ms
Approximately 4 kΩ
0–24 V DC
<4 V DC
>20 V DC
MG37N102

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt 525-690 v

Table of Contents