Download Print this page

Stall Protection (14) - Siemens 7SR17 Rho Manual

Motor protection relay

Advertisement

2.2

Stall Protection (14)

Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
If Gn 14-n Delay is small, gradually increase current until element operates.
If Gn 14-n Delay is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation
Apply 2x setting current if possible and record operating time
Phase
Gn 14–1 Setting
(Amps)
I
A
I
B
I
C
Phase
Gn 14–2 Setting
(Amps)
I
A
I
B
I
C
Phase
Gn 14–3 Setting
(Amps)
I
A
I
B
I
C
©2014 Siemens Protection Devices Limited
Chapter 6) 7SR17 Commissioning and Maintenance Guide
n/a
I
, I
, I
,
A
B
C
37, 46, 48/66, 49, 50BF, 50, 50N, 51, 51N, 60CTS
14-n Self Reset
Gn 14-1 Delay
P.U. Current
(sec)
Amps
Gn 14-2 Delay
P.U. Current
(sec)
Amps
Gn 14-3 Delay
P.U. Current
(sec)
Amps
Tol
Operate Time
2 x 14-1 Setting
Tol
Operate Time
2 x 14-2 Setting
Tol
Operate Time
2 x 14-3 Setting
Tol
Tol
Tol
Page 17 of 62