Chapter 4) 7SR17 Rho - Data Communications
Key
F# L
Fault Number low byte.
F# H
Fault Number high byte.
Meas
Measurand format R32.23, sent least significant byte first.
The following tables show the fields in the different event records as they are returned.
Byte
0
1
Content
1
0
Byte
0
1
Content
2
0
Byte
0
1
Content
4
0

4.2.6 EVENTCOUNT

The EVENTCOUNT register contains the current number of events in the relay's event buffer.
On reception this register should be interpreted as a 16 bit integer.
4.2.7 TIME_METER
The TIME_METER register contains the device's time. The time must be read or written in one step;
therefore the quantity should be 4 registers. Failing to do this will result in an exception code 2. The
time format is 8 bytes as follows.
The following table describes the fields in the time.
Key
ms L
Time Stamp Milliseconds low byte.
ms H
Time Stamp Milliseconds high byte.
Mi
Time Stamp Minutes (MSB = invalid, time not set > 23 hours).
Ho
Time Stamp Hours (MSB = Summer time flag).
Da
Time Stamp Days.
Mo
Time Stamp Months.
Ye L
Time Stamp Years low byte.
Ye H
Time Stamp Years high byte (Not Used).
The following table shows the fields in the time as they are returned.
Chapter 4 - Page 26 of 75
2
3
4
5
FUN INF
DPI
0
Event Type 1 Format.
2
3
4
5
RT
FUN INF
DPI RT L
Event Type 2 Format.
2
3
4
5
FUN INF
Meas
Event Type 4 Format.
Description
6
7
8
9
10
0
0
0
0
0
6
7
8
9
10
F# L F# H
0
0
H
6
7
8
9
10
0
0
0
Description
© 2013 Siemens Protection Devices Limited
11
12
13
14
15
ms
0
ms L
Mi
Ho
H
11
12
13
14
15
ms
0
ms L
Mi
Ho
H
11
12
13
14
15
ms
0
ms L
Mi
Ho
H