Chapter 3) 7SR17 Rho Performance Specification
2.17 87REF Restricted Earth Fault Protection
2.17.1 Reference
Parameter
Is
87REF Setting
t
87REF Delay setting
d
2.17.2 Operate and Reset Level
Attribute
I
Operate level
op
Reset level
Repeatability
Transient overreach
(X/R
100)
Variation
2.17.3 Operate and Reset Time
Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Overshoot time
Disengaging time
Chapter 3) Page 40 of 46
-10 °C to +55 °C
f
- 3 Hz to f
+ 2 Hz
nom
nom
Value
0.005, 0.006... 2.00 x In
0.00 ... 60 s
Value
100 % Is,
5 % or
1% x In
95 % I
,
5 % or
0.1% x In
op
1 %
-5 %
5 %
5 %
Value
2 x Is, 40 ms,
10ms
5 x Is, 30 ms,
10ms
t
+ t
,
1% or
10ms
basic
d
1% or
10ms
< 40 ms
< 50 ms