Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
Point
Name
FW#
Index
(Description)
0 Frequency
1 Vab Primary
2 Vbc Primary
3 Vca Primary
4 Va Primary
5 Vb Primary
6 Vc Primary
7 Va Secondary
8 Vb Secondary
9 Vc Secondary
21 Vzps
22 Vpps
23 Vnps
31 Ia Primary
32 Ib Primary
33 Ic Primary
34 Ia Secondary
35 Ib Secondary
36 Ic Secondary
37 Ia Nominal
38 Ib Nominal
39 Ic Nominal
43 In Primary
44 In Secondary
© 2013 Siemens Protection Devices Limited
Chapter 4) 7SR17 Rho - Data Communications
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Default
Default
Change Event
Variation
Assigned Class
Static
(1, 2, 3 or none)
Object 30
Object 32
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
Default
Variation
Default
Event
Multiplier
4
100.000
4
1.000
4
1.000
4
1.000
4
1.000
4
1.000
4
1.000
4
10.000
4
10.000
4
10.000
4
10.000
4
10.000
4
10.000
4
1.000
4
1.000
4
1.000
4
100.000
4
100.000
4
100.000
4
100.000
4
100.000
4
100.000
4
1.000
4
100.000
Chapter 4 - Page 61 of 75
Default
Deadband
1.000
10.000
10.000
10.000
10.000
10.000
10.000
1.000
1.000
1.000
1.000
1.000
1.000
10.000
10.000
10.000
0.100
0.100
0.100
0.100
0.100
0.100
10.000
0.100