Time Delayed Measured Earth Fault Protection (51G); Figure 3-15 Logic Diagram: Measured Time Delayed Earth-Fault Element - Siemens 7SR17 Rho Manual

Motor protection relay

Advertisement

Chapter 1) 7SR17 Rho Description Of Operation
3.4.3

Time Delayed Measured Earth Fault Protection (51G)

51G-n Setting sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC, ANSI or user specific curves using 51G-n Char. A time multiplier is applied to the
characteristic curves using the 51G-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be
chosen using 51G-n Char. When Definite Time Lag (DTL) is selected the time multiplier is not applied and the
51G-n Delay (DTL) setting is used instead. The full list of operating curves is given in Chapter 2 – 'Settings and
Instruments Guide'. Operating curve characteristics are illustrated in Chapter 3 – 'Performance Specification'.
The 51G-n Reset setting can apply a definite time delayed reset, or when the operation is configured as an IEC
or ANSI or user characteristic if the reset is selected as (IEC/ANSI) DECAYING reset the associated reset curve
will be used. The reset mode is significant where the characteristic has reset before issuing a trip output – see
'Applications Guide'.
A minimum operate time for the characteristic can be set using 51G-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using 51G-n Follower DTL setting.
Where directional elements are present the direction of operation can be set using 51G-n Dir. Control setting.
Directional logic is provided independently for each 51G element.
Operation of the time delayed overcurrent elements can be inhibited from
Inhibit 51G-n
51G-n VTSAction: Inhibit
Gn 51G-n Element
Disabled
Enabled
EF In
Inhibit 50G-n
51G Measurement
I
G
51G-n Dir
Control
Non Dir
Forward
Reverse
67G Fwd
67G Rev
Figure 3-15
Page 44 of 78
A binary or virtual input.
Operation of the VT Supervision function.
Gn 51G-n Setting
Gn 51G-n Charact
Gn 51G-n Time Mult
Gn 51G-n Delay (DTL)
&
Gn 51G-n Min. Op. Time
Gn 51G-n Follower DTL
Gn 51G-n Reset
En.
Dir En
En.
51G-n VTS
Action
Non Dir
Inhibit
VT Fail
&
1
&
If directional elements are not present this
block is omitted and 'Dir En' signal is set TRUE.
Logic Diagram: Measured Time Delayed Earth-fault Element
Pickup
General Pickup
trip
51G-n
&
&
51G-n
&
1
Dir En
©2014 Siemens Protection Devices Limited