4.7
T
C
RIP
IRCUIT
The relay provides three Trip Circuit Supervision elements.
One or more binary inputs can be mapped to Gn 74TCS-n. The inputs are connected into the trip circuit such that
at least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due
to a break in the trip circuit wiring or loss of supply an output is given.
The Gn 74TCS-n Delay setting prevents failure being incorrectly indicated during circuit breaker operation. This
delay should be greater than the operating time of the circuit breaker.
The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows
the user to realise several alternative monitoring schemes – see 'Applications Guide'.