Download Print this page

Danfoss VLT Flow Drive FC 111 Design Manual page 61

Hide thumbs Also See for VLT Flow Drive FC 111:

Advertisement

VLT® Flow Drive FC 111
Design Guide
Use the following graphs to determine if the output current must be derated based on switching frequency and ambient tempera-
ture. When referring to the graphs, I
[%]
I
out
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
0
2
5
0.37–1.5 kW (0.5–2.0 hp), 400 V, Enclosure Size H1, IP20
I
[%]
out
110 %
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
0
2
5
5.5–7.5 kW (7.4–10 hp), 400 V, Enclosure Size H3, IP20
I
[%]
out
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
5
0
2
18.5–22 kW (25–30 hp), 400 V, Enclosure Size H5, IP20
Danfoss A/S © 2021.04
indicates the percentage of rated output current, and f
out
40 C
104 F
45 C
113 F
50 C
122 F
f
[kHz]
sw
10
16
40 C
104 F
45 C
113 F
50 C
122 F
f
[kHz]
sw
10
16
40 C 104 F
45 C 113 F
50 C 122 F
f
[kHz]
sw
10
16
sw
I
[%]
out
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
0
2
5
2.2–4.0 kW (3.0–5.4 hp), 400 V, Enclosure Size H2, IP20
I
[%]
out
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
5
0
2
11–15 kW (15–20 hp), 400 V, Enclosure Size H4, IP20
I
[%]
out
110%
100%
80%
60%
40%
20%
2
4
6
30–37 kW (40–50 hp), 400 V, Enclosure Size H6, IP20
AJ363928382091en-000101 / 130R0983 | 61
Mechanical Installation
Considerations
indicates the switching frequency.
40 C
104 F
45 C
113 F
50 C
122 F
f
[kHz]
sw
10
16
40 C
104 F
45 C
113 F
50 C
122 F
f
[kHz]
sw
10
16
40 C 104 F
45 C 113 F
50 C 122 F
f
[ kHz ]
sw
8
10
12

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT Flow Drive FC 111 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel