Download Print this page

Danfoss VLT Flow Drive FC 111 Design Manual page 36

Hide thumbs Also See for VLT Flow Drive FC 111:

Advertisement

VLT® Flow Drive FC 111
Design Guide
Limit for R
≥120
sce
If the short-circuit power of the supply S
= 3  ×  R
  ×  U
S
SC
SCE
mains
at the interface point between the user's supply and the public system (R
The installer or user of the equipment is responsible for ensuring that the equipment is connected only to a supply with a short-
circuit power S
greater than or equal to what is specified above. If necessary, consult with the distribution network operator. Other
sc
power sizes can be connected to the public supply network by consultation with the distribution network operator.
Compliance with various system level guidelines: The harmonic current data in
IEC/EN 61000-3-12 with reference to the Power Drive Systems product standard. They may be used as the basis for calculation of the
harmonic currents' influence on the power supply system and for the documentation of compliance with relevant regional guide-
lines: IEEE 519 -1992; G5/4.
If there is a need for further reduction of harmonic currents, passive or active filters in front of the drives can be installed. Consult
Danfoss for further information.
3.4.5 Harmonics Emission Requirements
Equipment is connected to the public supply network.
Table 16: Connected Equipment
Options
Definition
1
IEC/EN 61000-3-2 Class A for 3-phase balanced equipment (for professional equipment only up to 1 kW (1.3 hp) total
power).
2
IEC/EN 61000-3-12 Equipment 16–75 A and professional equipment as from 1 kW (1.3 hp) up to 16 A phase current.
3.4.6 Harmonics Test Results (Emission)
Power sizes up to PK75 in T4 complies with IEC/EN 61000-3-2 Class A. Power sizes from P1K1 and up to P90K in T4 complies with
IEC/EN 61000-3-12, Table 4.
Table 17: Harmonic Current 0.37–22 kW (0.5–30 hp), 380-480 V
Actual 0.37–22 kW (0.5–30 hp), IP20, 380-480 V (typical)
Limit for R
≥120
sce
Actual 0.37–22 kW (0.5–30 hp), 380-480 V (typical)
Limit for R
≥120
sce
Table 18: Harmonic Current 30–90 kW (40–120 hp), 380-480 V
Actual 30–90 kW (40–120 hp), IP20, 380-480 V (typical)
Limit for R
≥120
sce
36 | Danfoss A/S © 2021.04
is greater than or equal to:
sc
  ×  I
  =   3  ×  120  ×  400  ×  I
equ
48
equ
).
sce
Table 13
to
Individual harmonic current I
I
5
36.7
40
Harmonic current distortion factor (%)
THDi
44.4
48
Individual harmonic current I
I
5
36.7
40
Harmonic current distortion factor (%)
Product Overview
46
Table 15
are given in accordance with
/I
(%)
n
1
I
I
7
11
20.8
7.6
25
15
PWHD
40.8
46
/I
(%)
n
1
I
I
7
11
13.8
6.9
25
15
AJ363928382091en-000101 / 130R0983
I
13
6.4
10
I
13
4.2
10

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT Flow Drive FC 111 and is the answer not in the manual?

Questions and answers