Planning
October 2022
Wire gauge
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2.3.1
Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter, which are installed
separately, is determined by cable type.
Cable type
Micro Motion 4-wire remote
mount
Micro Motion 9-wire remote
mount
User-supplied 4-wire
10
2
2
2
2
2
Wire gauge
Not applicable
Not applicable
VDC 22 AWG (0.326 mm²)
VDC 20 AWG (0.518 mm²)
VDC 18 AWG (0.823 mm²)
RS-485 22 AWG (0.326 mm²)
or larger
Resistance
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
Maximum length
•
1,000 ft (305 m) without
Ex-approval
•
500 ft (152 m) with IIC
rated sensors
•
1,000 ft (305 m) with IIB
rated sensors
60 ft (18 m)
300 ft (91 m)
500 ft (152 m)
1,000 ft (305 m)
1,000 ft (305 m)
Micro Motion 5700 transmitters for F
Installation Manual
MMI-20029969
Fieldbus
OUNDATION