5 | Operation
5.5.3.3.2 Characteristic C3 (dynamic filter monitoring)
Indicator
Measurement point 1
28
<
C3
%
3165
139.3
C1
m
3
/h
C2
kPa
1
2 3
4
Fig. 102: Frozen Display
72
Directory: \Configuration\Channel 3\Characteristic C3
Level: 3
Fig. 101: Characteristic C3 (dynamic filter monitoring)
Menu name
Displ.range C3 start
Displ.range C3 end
Channel ∆p
Channel Q
Approximation
∆p clean
∆p soiled
∆p correction value
Max. volume flow
Min. volume flow
Back
Frozen display
With the parameter
U
monitoring. The measured value for the soiling is frozen as soon as the volume
flow falls below this limit. This state is indicated in the display by the character
<
next to the measured value for the degree of soiling.
FISCHER Mess- und Regeltechnik GmbH
Characteristic C3
Displ.range C3 start
Displ.range C3 end
Channel ∆p
Channel Q
1
2 3
4
Description
This parameter defines the beginning
of the display range.
This parameter defines the end of the
display range.
A
This parameter defines the channel for
differential pressure measurement at
the filter.
A
This parameter is used to define the
channel for volume flow measurement.
A
This parameter defines the approxim-
ate formula for the volume flow meas-
urement.
This parameter defines the limit value
for the clean filter.
This parameter defines the limit value
for the dirty filter.
This parameter can be used to set an
offset for the characteristic curve.
This parameter determines the upper
limit value for the volume flow.
This parameter determines the lower
limit value for the volume flow. The
measured value is 'frozen' when the
volume flow falls below the limit value.
E
This represents the output (exit) of the
menu. This takes you back to the
Channel 3 menu..
Min. volume flow
defines the lower limit for the filter
U
A
A
BA_EN_DE90