5 | Operation
For example:
Red > Yellow > Green
5.5.1.5.3 Colour change C1 hysteresis
Functional principle:
64
Channel 1: Basic measuring range: 0 ... 100 Pa
The measuring range is defined as 10 ... 90 Pa. The green range should be 0
... 60 Pa. Then the critical range (yellow) up to 70 Pa starts. This is where the
red range that ranges up to the measuring range end at 90 Pa starts. The lower
colour changes red-yellow and yellow-green are switched off.
0
5
10
MS
S1
S2
Fig. 86: Example colour-change red/yellow/green
Meas.range C1 start
MS
Col.ch. C1 red-ylw
S1
Col.ch. C1 ylw-grn
S2
Col.ch. C1 grn/ylw
S3
Col.ch. C1 ylw/red
S4
Ms.range C1 end
ME
The lower colour changes S1 and S2 are 'switched off' by placing thresholds
outside the measuring range. If the threshold values were to be laid precisely at
the start of the measuring range, the display would shine red in the zero-point,
The cause for this lies in the priority of the colours. The red colour has priority
over the yellow colour and this has priority over the green colour.
Directory: \Configuration\Channel 1\Colour change C1\Col.ch. C1 hyst.
Level: 4
Col.ch. C1 hyst.
1
Fig. 87: Colour change C1 hyst.
This parameter can be used to define an hysteresis for the switch thresholds of
the colour change. The set hysteresis applies to all switch thresholds at the
same time. The input is a pressure value in the current unit. The allowed value
range is stated automatically.
The colour symbolises the following risk levels:
Colour
Risk level
Green
0
yellow
1
rot
2
FISCHER Mess- und Regeltechnik GmbH
Basic measuring range
60
GREEN
S3
10 Pa
5 Pa
5 Pa
60 Pa
70 Pa
90 Pa
10.000
Edit
OK Cancel
2 3
4
Operating mode
Normal
Warning
Danger
70
90
YELLOW
RED
S4
ME
< MS
< MS
U
Pa
BA_EN_DE90
100 Pa