5 | Operation
5.5.1.2.3 Measuring range C1 end
5.5.1.2.4 Damping C1
50
Directory: \Configuration\Channel 1\Measurement C1\Meas.range C1 end
Level: 4
Meas.range C1 End
1
Fig. 62: Meas.range C1 end
At this point, the end value of the measuring range is entered. The value range
and its limits are displayed automatically.
Directory: \Configuration\Channel 1\Measurement C1\Damping C1
Level: 4
\...\...\...\Damping C1
1
Fig. 63: Damping C1
If there are unsteady measurement readings during operation, you can use the
Damping C1
parameter
The value range is from 0 s to 30 s.
The parameter functions like a capillary throttle. Please note that the damping
only affects the signal input. The measuring cell itself is not uninfluenced. The
parameter value states the time period until the amplitude reaches 90 %. A
value of 0s means that no damping is carried out.
FISCHER Mess- und Regeltechnik GmbH
080.000
Edit
OK
Cancel
2 3
4
0
Edit
OK
Abbr.
2 3
4
to stabilise the reading.
U
Pa
U
s
BA_EN_DE90