5.5.1.2.5 Offset C1
BA_EN_DE90
Directory: \Configuration\Channel 1\Measurement C1\Offset C1
Level: 4
\...\...\...\Offset C1
1
Fig. 64: Offset C1
If the measuring data display in the zero-point shows a different value, this can
be corrected with the parameter
The value range is one third of the basic measuring range.
The current measurement is shown at the bottom right. During the input, the set
offset parameters act immediately on the measured value. Please note that this
zero-point window and the damping are not active during the offset setting.
Ideal characteristic curve
Fig. 65: Offset error
The parameter causes a shift of the entire characteristic toward the ideal char-
acteristic.
0.000
Edit
OK
Cancel
0.087
2 3
4
Offset C1
.
Operation | 5
U
Pa
Current measured value
Pa
Real characteristic curve
Differential pressure
51