Safety
Rating
Mechanical
Information
Data
Installation
2
Rating Data
Figure 2-1 Model code explanation
SK A 1 2 XXXXX
Table 2-1 Commander SK 200V units
Nominal
motor
Model
power
Number
kW
hp
SKA1200025 0.25
0.33
SKA1200037 0.37
0.5
SKA1200055 0.55
0.75
SKA1200075 0.75
1.0
SKBD200110
1.1
1.5
SKBD200150
1.5
2.0
SKCD200220
2.2
3.0
Table 2-2 Commander SK 400V units
Nominal
motor
Model
power
Number
kW
hp
SKB3400037 0.37
0.5
SKB3400055 0.55
0.75
SKB3400075 0.75
1.0
SKB3400110
1.1
1.5
SKB3400150
1.5
2.0
SKC3400220
2.2
3.0
SKC3400300
3.0
3.0
SKC3400400
4.0
5.0
Output frequency: 0 to 1500Hz
Output voltage: 3 phase, 0 to drive rating (240 or 480Vac maximum set by Pr 08).
The output voltage can be increased by 20% during deceleration. See Pr 30 on page 27
NOTE
The maximum continuous current inputs are used to calculate input cable and fuse
NOTE
sizing. Where no maximum continuous input currents are indicated, use the typical full
load input current values. See Commander SK Product Data Guide for cable and fuse
data.
Commander SK Getting Started Guide
Issue Number: 1
Electrical
Keypad
Parameters
Installation
and Display
Drive kilowatt rating: 00025 = 0.25kW
Drive voltage rating: 2 = 230V, 4 = 400V
Number of input phases: 1 = 1phase, 3 = 3phase, D = 1 and 3phase
Frame size
Model: Commander SK
Typical
full load
Supply
input
voltage and
current
frequency
A
1ph
3ph
4.3
1 phase
5.8
200 to
240Vac ±10%
8.1
48 to 62Hz
10.5
1/3 phase
14.2
6.7
200 to
17.4
8.7
240Vac ±10%
23.2 11.9
48 to 62Hz
Typical
full load
Supply
input
voltage and
current
frequency
A
1.7
2.5
3.1
3 phase
4.0
380 to
480Vac ±10%
5.2
48 to 62Hz
7.3
9.5
11.9
www.controltechniques.com
Quick Start
Diagnostics Options
Commissioning
Maximum
100% RMS
continuous
output
input
current
current
A
A
1ph
3ph
Heavy Duty
1.7
2.2
3.0
4.0
9.2
5.2
12.6
7.0
17.0
9.6
Maximum
100% RMS
continuous
output
input
current
current
A
A
Heavy Duty
2.5
1.3
3.1
1.7
3.75
2.1
4.6
2.8
5.9
3.8
9.6
5.1
11.2
7.2
13.4
9.0
Parameter
UL Listing
List
Information
150%
Minimum
overload
braking
current for
resistor
60s
value
A
Ω
2.55
68
3.3
68
4.5
68
6.0
68
7.8
28
10.5
28
14.4
28
150%
Minimum
overload
braking
current for
resistor
60s
value
A
Ω
1.95
100
2.55
100
3.15
100
4.2
100
5.7
100
7.65
100
10.8
55
13.5
55
7
Need help?
Do you have a question about the Commander SK and is the answer not in the manual?