Pin Allocation Table; Digital Terminal - Festo MPS PA Station Operating Instructions Manual

Bottling learning system
Hide thumbs Also See for MPS PA Station:
Table of Contents

Advertisement

Work and safety instructions

6.2 Pin allocation table

6.2.1 Digital terminal

I/O
Reference
designation
I0
-TF1
I1
-BG2
I2
-BG3
I3
-BG4
I4
-BG5
I5
-BG6
I6
I7
-KF10
Q0
-MA1
Q1
-MB2
Q2
-MA31 / -
MA32
Q3
-MB4
Q4
-MA5
Q5
Q6
Q7
24 V A
24 V B
GND A
GND A
GND B
Note
Cable jumpers are connected from emergency off to bit 1.5 on all preferred PLC versions.
18
Designation
Switch point comparator, level reached, ultrasonic sensor BL1 Tank VE2
Capacitive proximity switch, upper limit of the storage tank VE1
Capacitive proximity sensor, lower limit of the storage tank VE1
Diffuse light sensor, bottle at the beginning of the conveyor
Diffuse light sensor, bottle at the filling position
Diffuse light sensor, bottle at the end of the conveyor
Overflow alarm of the relay contact, collection error
Motor pump PL1 ON, conveying into the filling container
Solenoid valve V403 OPEN, filling bottle
Conveyor motors ON, bottle transport forward
Activate the separator, separate the bottle
Motor PL2 pump ON, conveying to the next station
24 V power supply for outputs
24 V power supply for inputs
0 V power supply for outputs
0 V power supply for outputs
0 V power supply for inputs
Bottling Learning System
Terminal
SysLink
SysLink
Pin
Wire color
9
13
Gray-pink
10
14
Red-blue
11
15
White-green
12
16
Brown-green
13
17
White-
yellow
14
18
Brown-
yellow
15
19
White-gray
16
20
Gray-brown
1
1
White
2
2
Brown
3
3
Green
4
4
Yellow
5
5
Gray
6
6
Pink
7
7
Blue
8
8
Red
24 VA
9+10
Black
24VB
21+22
White-pink
GND A
11
Brown-pink
GND A
12
Purple
GND B
23+24
White-blue
© Festo Didactic 696690

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents