Occupancy Inputs; Blink Warn - Leviton EZ-MAX User Manual

Relay products
Hide thumbs Also See for EZ-MAX:
Table of Contents

Advertisement

OccSen:
3
LOCAL
BLINK WARN: YES
OccSen:
3
LOCAL
BLINK WARN: YES
OccSen:
3
LOCAL
RTG DELAY:000sec
Page 76
Repeat Steps 8 - 19 as necessary for every button on every station you
Step 20:
are programming.
Assign actions just as for a local switch.
Step 21:

Occupancy Inputs

The process for setting up Occupancy Sensors as inputs to your Z-Max relay cabinet is
identical to low voltage switches except that the type should be defined as OCC.
When assigning actions to occupancy inputs, the following three behaviors can be
assigned to the input:
• NORM ON - AUTO OFF: When the occupancy sensor detects movement and goes
active, relays assigned to this input will turn on only if all relays have been off for
more than the Re-trigger Delay time (set later). Relays will turn off when the
occupancy sensor goes inactive after the Off Delay time (set later). This scenario is
used to hold off reactivating the relays by the sensor when one or more lights has
been manually turned off to temporarily adjust the lighting levels in the room.
• ALWA ON - AUTO OFF: When the occupancy sensor detects movement and goes
active, relays assigned to this input will turn on. Relays will turn off when the
occupancy sensor goes inactive after the Off Delay time (set later).
• MAN ON - AUTO OFF: If the input is set to this behavior, the occupancy sensor has
no effect on the relays when it goes active. Instead, the relays must be turned on
via any other means (typically a switch input). When the occupancy switch goes
inactive it will turn off the relays. This application is good for when manual control
is desired from a switch but you want the lights to turn off when someone forgets
to turn them off. This functional operation is required by California Title 24 in most
applications.
Additionally, when setting up occupancy inputs, several additional questions are
asked:

Blink Warn

Indicates whether or not a blink warn should be issued before turning off the lights
associated with this occupancy sensors.
Delay from vacancy until lights off
Allows you to set a delay between when the occupancy sensor indicates that the room
has become vacant and the lights turn off.
Re-trigger Delay
Allows you to set a mandatory delay between when the lights are turned off (by
occupancy sensor or other method) and the earliest point at which the lights can be
turned on, regardless of occupancy state.
If the occupancy sensor used already has an
internal delay, the off delay time will be added to
the sensor delay. When using sensors with
internal delay, set delay to 0 (default)