4.3.3.3 Alarm Logic Table
Flow Alarm
Single
Single
Dual
Dual
NOTE:
The NPN and PNP have different outputs when used due to their wiring.
Using the NPN: OFF =Powered +VDC and ON = Unpowered 0VDC
Using the PNP: OFF=Unpowered 0VDC and ON = Powered +VDC

4.3.3.4 Analog Outputs

NOTE:
FOR FULL ANALOG OUTPUT FUNCTION EXTERNAL POWER OF >15VDC IS
NOTE:
© Titan Enterprises Ltd
Invert
Unticked
Ticked
Unticked
Ticked
REQUIRED
The 4-20mA is ACTIVE
Incorrect wiring may damage this device
www.flowmeters.co.uk
Alarm Action
Below Threshold
OFF
ON
In Range
ON
OFF
Analog Output: there are four options on the
drop-down menu:
Not Used
4-20mA (active)
0-5 Volt
0-10 Volt.
(Not
loop powered).
Once the Analog Mode selection has been
made you can enter the low and high flows
for the analog outputs as required. These are
numeric entries in the units and time base
selected in calibration settings.
PulsiteLink_Instruction_Manual_0722
Above Threshold
ON
OFF
Outside Range
OFF
ON