4.3.3.2.2
Single Flow Alarm:
Checking this option opens up input boxes for
, Hysteresis
Threshold
Threshold
Set the
transistor to operate.
The logic of operation can be adjusted with the
Invert
check box.
Hysteresis (%)
: This is used to prevent "fluttering" of
the alarm signal when flow is around the threshold
level.
The % value is set around the Threshold value.
For example: Threshold Set at 1.0 and Hysteresis at
20%. The Pin will turn ON at 1.1 and off at 0.9.
NOTE:
The INVERT checkbox will reverse the
action of the alarm output.
For details for each PIN see the or hover mouse over the set point to see the action of the
output with the chosen settings.
© Titan Enterprises Ltd
Invert.
and
to the flow value you require the
www.flowmeters.co.uk
PulsiteLink_Instruction_Manual_0722
17