Fct. 3.06 APPLICAT.
Press key → .
→ FLOW = Set characterization for the flow,
STEADY
(flow is steady)
PULSATING
(pulsating flow, e.g. due to reciprocating pumps,
see also Sect. 6.4, 6.5 and 6.6
"Special-case applications")
Press ↵ key to return to Fct. 3.06 APPLICAT.
Fct. 3.07 MEAS.PNT.
Press key → .
Set measuring point identification using max. 10 characters , (e.g. TQ1_532197)
You can use any out of A...Z / a...z / 0...9 or _ (underscore)
Select character by pressing key ↑ or ↓.
-
Use key → to shift one place to the left, back with ← key.
-
Press key ↵ to return to Fct. 3.07 MEAS.PNT.
Fct. 3.08 COM
Press key → .
Specify function
OFF
(Switched off)
HART
(HART Interface)
KROHNE (RS 485 Interface)
Use key ↑ or ↓ to set ADDRESS 00-15 after selecting "HART" with → key.
Press key ↵ dto return to Fct. 3.08 COM.
Use key ↑ or ↓ to set ADDRESS 000-239 after selecting "KROHNE" (RS 485). Press key → and
set up BAUD RATE: • 1200 • 2400 • 4800 • 9600 • 19200. Use key ↑ or ↓ to select baud rate.
Press key ↵ to return to Fct. 3.08 COM.
Fct. 1.08 CTRL.INP. E
Press key → .
Select control input function, using key ↑ or ↓.
OFF
ZERO OUTPUT
RESET COUNT.
RESET ERROR
Press key ↵ to return to Fct. 1.08 CTRL.INP. E
For factory-set preferences refer to the start-up protocol and Section 3.2.
(Switched off, out of function)
(Set output and display to "Min. values")
(Reset counter)
(Delete / confirm error message)
Installation and operating instructions IFC 020
press key
Measuring point identification
Communication interface
}
select function using key ↑ or ↓
Control input E (IFC 020 E only)
Applications
5.15
}
select function using
key ↑ or ↓
5.16
5.17
5.18
5/12