If you need to return the device to the manufacturer or supplier, please fill out the form • contained on the CD-ROM and send it with the device. Unfortunately, the manufacturer cannot repair or inspect the device without the completed form. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
1 Device in the version as ordered 2 Documentation (calibration report, Quick Start, CD-ROM with product documentation for measuring sensor and signal converter) 3 Signal cable (only for remote version) www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat • exchanger. • Do not expose the signal converter to intense vibration. The flowmeters are tested for a vibration level in accordance with IEC 68-2-3. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
1 Prepare the holes with the aid of the mounting plate. For further information refer to Mounting plate, wall-mounted version on page 8. 2 Fasten the device securely to the wall with the mounting plate. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
Page 7
INSTALLATION IFC 100 Mounting multiple devices next to each other [mm] [inches] Ø6.5 Ø0.26 87.2 12.2 10.1 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
Ensure that the sensor constant GK/GKL (see type plates) are identically set. • If delivered separately or when installing devices that were not configured together, set the converter to the DN size and GK/GKL of the sensor. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
A shielded two-wire copper cable is used as the field current cable. The shielding MUST MUST be MUST MUST connected in the housing of the measuring sensor and signal converter. INFORMATION! The field current cable is not part of the scope of supply. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
• Insulated conductor / insulated conductor 1000 V • Insulated conductor / outer shield 1000 V Twisting of the insulated conductors • At least 10 twists per meter, important for screening magnetic fields. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
1 Maximum length of signal cable A between the measuring sensor and signal converter [m] 2 Maximum length of signal cable A between the measuring sensor and signal converter [ft] 3 Electrical conductivity of the medium being measured [μS/cm] 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
4 Crimp the wire end ferrules onto the stranded drain wire. 5 Crimp the wire end ferrules onto the conductors (2, 3). 6 Pull the heat-shrinkable tubing over the prepared signal cable. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
2 x 0.75 Cu 2 x 18 150...300 500...1000 2 x 1.50 Cu 2 x 14 300...600 1000...2000 2 x 2.50 Cu 2 x 12 1 Cu = copper cross-section 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
Page 16
3 Slide an insulating tube over the stranded drain wire. 4 Crimp a wire end ferrule onto the stranded drain wire. 5 Crimp wire end ferrules onto the conductors. 6 Pull a shrinkable tube over the prepared cable. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
4 Slide an insulating tube over the stranded drain wire (1). 5 Crimp the wire end ferrules onto conductors 2 and 3 and the stranded drain wire (1). 6 Pull the heat-shrinkable tubing over the prepared signal cable. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
2 Trim the outer shield to dimension b and pull it over the outer sheath. 3 Crimp wire end ferrules onto both conductors. 4 Pull a shrinkable tube over the prepared cable. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
Observe without fail the local occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
2 Lift the housing at the top and bottom at the same time. 3 Slide the housing cover upward. 4 The housing cover is guided and held by the inside hinge. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
Page 21
6 Stranded drain wire (1) of the inner shield (10) of the signal cable 7 Electrical conductor (2) 8 Electrical conductor (3) 9 Stranded drain wire (S) of the outer shield (60) 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
Figure 3-10: Connection diagram for signal and field current cable 1 Electrical terminal compartment in signal converter 2 Signal cable A 3 Field current cable C 4 Electrical terminal compartment in measuring sensor 5 Functional ground FE www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
• The documentation for the measuring sensors also contain descriptions on how to use grounding rings and how to install the measuring sensors in metal or plastic pipes or in pipes which are coated on the inside. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
1 Retaining band of the cover 2 Cable entry power supply remote version 3 Cable entry power supply compact version Version overview Version Non-Ex 100...230 VAC Standard Optional 12...24 VDC Standard 24 VAC/DC Standard www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
Page 25
(PELV) (acc. to VDE 0100 / VDE 0106 and IEC 364 / IEC 536 or relevant national regulations). INFORMATION! 12 V is not not included in the tolerance range. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
® + HART active 1 function changed by reconnecting 2 changeable Description of used abbreviations Current output active or passive Pulse/frequency output passive Status output / limit switch passive www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
• Push the prepared cables through the cable entries and connect the necessary conductors. • Connect the shield. • Close the housing cover. INFORMATION! Ensure that the housing gasket is properly fitted, clean and undamaged. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
2 Tighten the screw connection of the cable entry securely. 3 Seal cable entries that are not needed with a plug. www.krohne.com 07/2010 - 4000124104 - QS IFC 100 R04 en...
It is possible to change between the two measured value windows, the trend display and the list with the status messages by pressing the keys ↑ and ↓. 07/2010 - 4000124104 - QS IFC 100 R04 en www.krohne.com...
Page 32
Measuring systems for the oil and gas industry • Measuring systems for sea-going tankers Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 D-47058 Duisburg (Germany) Tel.:+49 (0)203 301 0 Fax:+49 (0)203 301 10389 info@krohne.de The current list of all KROHNE contacts and addresses can be found at: www.krohne.com...