E50F2A, E50F5A Installation Guide

Troubleshooting

China RoHS
Compliance
Information -
Environment Friendly
Use Period (EFUP)
Table
ZL0119-0F
Page 34 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Problem
The maintenance wrench
There is a problem with the inputs to the power meter.
icon appears in the power
meter display.
The meter is not receiving adequate power.
The display is blank after
applying control power to
the meter.
Values from power network
LonMark resource files of versions lower than 13.04 have the
variables appear 3.4 times
default format in the U.S. for SNVT_power_f variables in
higher than expected.
Btu/hr.
Incorrect setup values
Incorrect voltage inputs
The data displayed is
inaccurate.
Power meter is wired improperly.
部件名称
Part Name
(Pb)
电子件
X
Electronic
本表格依据SJ/T11364的规定编制。
O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572规定的限量要求。
(企业可在此处,根据实际情况对上表中打
This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below
the limit as stipulated in GB/T 26572.
X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part
is above the limit as stipulated in GB/T 26572
Z000057-0B
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Cause
Hazardous Substances
有害物质 -
(Hg)
(Cd)
(Cr (VI))
六价铬
O
O
O
的技术原因进行进一步说明。)
Solution
See the Alert sub-menu or the Diagnostic Alert
Modbus Register 146.
Verify that the meter control power are
receiving the required voltage.
Verify that the heart icon is blinking.
Check the fuse.
See the section on "Formatting Power Correctly."
Verify the values entered for power meter setup
parameters (CT and PT ratings, system type,
etc.).
Check power meter voltage input terminals to
verify adequate voltage.
Check all CTs and PTs to verify correct
connection to the same service, PT polarity,
and adequate powering. See the Wiring
Diagrams section for more information.