Download Print this page

Troubleshooting - Veris Industries H8030 Installation Manual

Advertisement

float multiPliers
Addr
Units
40257
kWh
40258
kWh
40259
kWh
40260
kWh
40261
kW
40262
kW
40265
VA
40266
VA
40275
kW
40276
kW
40281
---
40282
---
40287
Volts
40288
Volts
40299
Amps
40300
Amps
40305
kW
40306
kW
40307
kW
40308
kW
40309
kW
40310
kW
Z205220-0C
PAGE 7
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H8030/8031
100A/300A
Multiplier
2
2
2
2
2
1
1
1
1
1
1
2
2
2
©2009 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
INSTALLATION GUIDE

troubleshooting

Problem
Status LED does not blink
Check fuses and voltage connections. Status
LED should blink regardless of CTs, Modbus
connections, and DIP switch setting.
Power meter interferes with
Set DIP switches to a different Modbus address
another device Modbus.
which is not in use.
Readings seem highly
• In most cases, incorrect wiring will cause the
inaccurate.
STATUS LED to blink RED (slowly). However, a
power factor lower than 0.5 could cause the LED
to blink this way, even if the unit is installed
properly.
• It does not matter which side of the CT faces
towards the load.
• Check actual current with Amp clamp. Expected
power is: kW = Volts x Amps x 1.732 x PF / 1000;
kW = Horsepower x 0.746 (PF is usually 0.7 to
0.95 depending on the nature of the load)
• Compare this to the kW. If current is below 7%
of full scale maximum for the CT, use a smaller
CT or wrap each wire through the CT multiple
times
Meter goes offline when load
Voltage leads must be connected on the Line
is switched off.
side of the conductor. The power meter cannot
communicate without voltage.
Status LED blinks red.
• If the LED blinks quickly (i.e., about 5 blinks in
two seconds) the CT used is too small. Replace
with a larger CT.
• If the LED blinks slowly (i.e., about 1 blink
in two seconds) the CT is not installed on the
correct conductor, or the power factor is less
than 0.5. The meter can accurately measure
these low PFs, but few loads operate normally at
such a low power factor.
Solution