E50F2A, E50F5A Installation Guide
Network Variables (cont.)
NV
Function
NV Name
Num.
Block
PULSE COUNTERS
nvoPulseCount1
37
Meter
nvoPulseCount2
38
Meter
nviPulseCntReset
33
Meter
DIAGNOSTICS
nvoAlert
96
Meter
nvoStartupCount
94
Meter
nvoMeterTime
90
Meter
nviTimeSet
7
NodeObject
nvoMaxSysPower
92
Meter
nvoFullFwVersion
91
Meter
ZL0119-0F
Page 27 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Type
Units
SNVT_count_32
-
SNVT_count_32
-
SNVT_switch
-
SNVT_state
-
SNVT_count
-
SNVT_time_stamp
-
SNVT_time_stamp
-
SNVT_power_f
W
SNVT_str_asc
-
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Propagation Control
Log
Configuration
Point
Control
Property
Index
Type
Name
43
cpPulseCount1
Min Delta
45
cpPulseCount2
Min Delta
-
-
-
-
cpAlert
Heartbeat
-
cpStartupCount
Heartbeat
-
None
-
-
-
-
-
None
-
-
None
Polled
Description
Pulse Counter 1 (enabled on E50F2A and E50F5A)
Pulse Counter 2 (enabled on E50F5A only)
Clear the pulse counter(s). To reset, set the state field to 1
and the value field to greater than 0.
Diagnostic Alert Bitmap. 1 = Active
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 to 65 Hz, or
insufficient voltage to determine frequency
Bit 7: Internal data bus communication problem
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases
having a PF less than 0.5 due to mis-wiring of phases
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Not used
Bit 15: Not used
Power Up Counter.
Meter Time.
Set the Meter Time. Meter time does not have battery
backup and will therefore reset to the millennium
when power is lost to the meter. This input is polled on
startup, and time is restored if this input is bound to a
time source.
Theoretical Maximum System Power. This value is the
theoretical maximum power the meter expects to see,
based on the System Type, CT size, and System Voltage.
It is updated whenever of these values change.
Reset System, Operating System, and Gateway revision
numbers in an ascii string (e.g. "RSx.yyy OSx.yyy
Gateway x.yyy")