Veris Industries E50F2A Installation Manual page 33

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide
Configuration Properties (cont.)
CP Name
Type
LOGGING (E50F5 ONLY)
cpLoggingPoint1
UCPTlogPoint1
(UCP_Type_13
w/o resource files)
(SNVT_count ref.)
cpLoggingPoint2
UCPTlogPoint2
(UCP_Type_14 w/o
resource files)
(SNVT_count ref.)
cpLoggingPoint3
UCPTlogPoint3
(UCP_Type_15 w/o
resource files)
(SNVT_count ref.)
cpLoggedData
SCPTminSendTime
cpLogConfig
UCPTlogConfig
(UCP_Type_12 w/o
resource files)
(SNVT_state ref.)
ZL0119-0F
Page 33 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
NV Num.
R/W
Applies To
23
R/W
"Meter" Function
Block
24
R/W
"Meter" Function
Block
25
R/W
"Meter" Function
Block
27
R/W
nvoLoggedData
26
R/W
"Meter" Function
Block
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
Default Value
See description
nvoRealEnergy
(257)
See description
nvoReactEnergy
(311)
See description
nvoPresRealDmnd
(325)
0 - 0.3 seconds
0.1 seconds (1
(0 - 3 raw)
raw)
See description
Bit 0: 0
(Continuous log
buffer mode)
Bit 1: 0 (Logging
Enabled)
Description
Set to the index of the network variable to
log. Indices are provided as a column in the
network variable table above.
Set to the index of the network variable to
log. Indices are provided as a column in the
network variable table above.
Set to the index of the network variable to
log. Indices are provided as a column in the
network variable table above.
Throttle for log download. Defaults to 100ms
(20 packets per second for log download using
Acknowledged service). Any change from this
value will affect the speed of log download
(i.e. 200 msec will use half of the packets
per second but cause the length of the log
download to double).
Logging Configuration.
Bit 0: Clear to 0 for continuous (circular,
overwriting old date when full) log buffer
mode. Set to 1 for single shot logging mode
(stops when log is full).
Bit 1: Clear to 0 to enable logging. Set to 1 to
halt logging.
TM
0119