Configuration Properties - Veris Industries E50F2A Installation Manual

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide

Configuration Properties

CP Name
Type
INFORMATION
cpMeterModel
SCPTpartNumber
cpSerialNumber
SCPTserialNumber
cpDevMajVer
SCPTdevMajVer
cpDevMinVer
SCPTdevMinVer
INSTALLATION DETAILS
cpSystemType
UCPTsystemType
(UCP_Type_3 w/o
resource files)
(SNVT_count ref.)
cpDisplayUnits
UCPTdisplayUnits
(UCP_Type_4 w/o
resource files)
(SNVT_count ref.)
cpCtPriRatio
UCPTctPriRatio
(UCP_Type_5 w/o
resource files)
(SNVT_count ref.)
cpPtRatio
UCPTptRatio (UCP_
Type_7 w/o resource
files)
(SNVT_count ref.)
cpSystemVoltage
UCPTsysVoltage
(UCP_Type_8 w/o
resource files)
(SNVT_count ref.)
cpPhaseLossVolt
UCPTphLossVolt
(UCP_Type_9 w/o
resource files)
(SNVT_count ref.)
ZL0119-0F
Page 30 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
NV Num.
R/W
Applies To
-
R
"Meter" Function
Block
-
R
"Meter" Function
Block
-
R
"NodeObject"
Function Block
-
R
"NodeObject"
Function Block
12
R/W
"Meter" Function
Block
13
R/W
"Meter" Function
Block
14
R/W
"Meter" Function
Block
16
R/W
"Meter" Function
Block
17
R/W
"Meter" Function
Block
18
R/W
"Meter" Function
Block
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
Default Value
-
-
-
-
-
-
-
-
10, 11, 12,
40
31, 40
0, 1
1 (IEEE)
20 - 5000(A)
100(A)
1 – 32000
100 (scaled 1:1)
(scaled 0.01-
320.00)
82 - 32000
600(VL-L)
(VL-L)
1 - 99 (%)
10(%)
Description
Meter Manufacturer and Model, stored as an
ASCII string (e.g. "Veris Industries E50F2A").
Meter Serial Number.
Firmware Major Version (Gateway). See
nvoFullFwRevision for RS, OS firmware
revisions.
Firmware Minor Version (Gateway). See
nvoFullFwRevision for RS, OS firmware
revisions.
System Type (see installation instructions for
more detail).
10 Single Phase: A + N
11 Single Phase: A + B
12 Single Split Phase: A + B + N
31 3 Phase Delta, A + B + C, no N
40 3 Phase Wye, A + B + C + N
Note: Only the indicated phases are monitored
for phase loss.
Screen Display Units
0 = IEC (U, V, P, Q, S)
1 = IEEE (VLL, VLN, W, VAR, VA)
CT Ratio – Primary (from CT rating)
PT Ratio. This value is scaled by 100 (200 = PT
ratio of 2:1). Set to 100 (1.00:1) for no PT.
System Voltage. This voltage is line to line
unless the system type is 10, where it is line
to neutral. The meter refuses voltages that
are outside of the range of 82-660 volts when
divided by the PT Ratio (above).
Phase Loss Voltage Threshold in percent of
system voltage. Any phase (as configured
by nviSystemType) whose level drops below
this threshold triggers a Phase Loss alert.
For example, with the system type set to 40
(3L+N) and the System voltage set to 480V
L-L, the L-N voltage for each phase should
be 277V. When this threshold is set to 10%,
if any phase drops to less than 10% of 277V
(less than 27.7V), or if any L-L voltage drops
to less than 10% of 480V (less than 48V), the
corresponding phase loss alarm bit in nvoAlert
is set to 1.