E50F2A, E50F5A Installation Guide
Configuration Properties (cont.)
CP Name
Type
cpPhaseLossImbal
UCPTphLossImbal
(UCP_Type_10 w/o
resource files)
(SNVT_count ref.)
cpDemSubintLen
UCPTDemSubintLen
(UCP_Type_11
w/o resource files)
(SNVT_count ref.)
cpDemSubintCnt
UCPTDemSubintCnt
(UCP_Type_1 w/o
resource files)
(SNVT_count ref.)
PROPAGATION CONTROL
cpMaxNvSntPerSec UCPTnvUpdtLimit
(UCP_Type_2 w/o
resource files)
(SNVT_count)
cpAllEnergy
SCPTminSndT
cpAllPower
SCPTminSndT
cpAllVoltage
SCPTminSndT
ZL0119-0F
Page 31 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
NV Num.
R/W
Applies To
19
R/W
"Meter" Function
Block
20
R/W
"Meter" Function
Block
21
R/W
"Meter" Function
Block
29
R/W
"Meter" Function
Block
1
R/W
All energy output
network variables
2
R/W
All power output
network variables
3
R/W
All voltage output
network variables
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
Default Value
1 - 99 (%)
25(%)
0, 10 - 32767
900 (seconds)
(seconds)
1 - 6
1
0 - 65535
10
0 - 1 hour,
15 seconds
49 minutes,
13 seconds,
500ms (6553.5
seconds)
0 - 1 hour,
15 seconds
49 minutes,
13 seconds,
500ms (6553.5
seconds)
0 - 1 hour,
15 seconds
49 minutes,
13 seconds,
500ms (6553.5
seconds)
Description
Phase Loss Imbalance Threshold in percent. For
a 3-phase Y(3+N) system (type 40), both Line
to Neutral and Line to Line voltages are tested.
In a 3-phase delta system (type 31), only the
Line to Line voltages are examined. In a single
split-phase (2+N) system (type 12), just the
Line to Neutral voltages are compared.
Sub-Interval Length in seconds. For sync-to-
comms, set this to 0 and use nviDemSubintRes
to externally restart the sub-interval.
Number of Sub-Intervals per Demand Interval.
Sets the number of sub-intervals that make
a single demand interval. For block demand,
set this to 1.
Limits the total number of updates sent out per
second for network variables in the following
categories: Energy, Power, Voltage, Current,
Power Factor, Frequency, Pulse Counters,
Startup Count, and Alerts. If more than the
number of updates specified is queued to be
sent out in any 1 second period, the excess
updates are delayed until the next second
to reduce network traffic. This configuration
property is provided to give rough burst
control. The number of packets sent per
second will vary based on the connection
types (ACK, UNACK, etc.) and updates from
other network variables that are not controlled
by this configuration property.
Throttle for all energy output network variables.
After propagation of a network variable,
updates to the same network variable are
blocked for the time set by this configuration
property. The configuration property is shared,
but each energy output network variable has
its own independent throttle counter that
resets to the value specified by this CP after it
has been propagated.
Throttle for all power output network variables.
After propagation of a network variable,
updates to the same network variable are
blocked for the time set by this configuration
property. The configuration property is shared,
but each power output network variable has
its own independent throttle counter that
resets to the value specified by this CP after it
has been propagated.
Throttle for all voltage output network
variables. After propagation of a network
variable, updates to the same network
variable are blocked for the time set by this
configuration property. The configuration
property is shared, but each voltage output
network variable has its own independent
throttle counter that resets to the value
specified by this CP after it has been
propagated.