E50C1 Installation Guide

Troubleshooting

China RoHS
Compliance
Information -
Environment Friendly
Use Period (EFUP)
Table
ZL0101-0D
Page 20 of 20
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Problem
The maintenance wrench icon
appears in the power meter display.
The display is blank after applying
control power to the meter.
The data displayed is inaccurate.
Cannot communicate with power
meter from a remote personal
computer.
部件名称
Part Name
(Pb)
电子件
X
Electronic
本表格依据SJ/T11364的规定编制。
O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572规定的限量要求。
(企业可在此处,根据实际情况对上表中打
This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below
the limit as stipulated in GB/T 26572.
X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part
is above the limit as stipulated in GB/T 26572
Z000057-0B
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Cause
There is a problem with the
See the Alert sub-menu or the Diagnostic Alert Modbus Register
inputs to the power meter.
146
The meter is not receiving
Verify that the meter control power are receiving the required
adequate power.
voltage.
Verify that the heart icon is blinking.
Check the fuse.
Incorrect setup values
Verify the values entered for power meter setup parameters (CT
and PT ratings, system type, etc.). See the Setup section.
Incorrect voltage inputs
Check power meter voltage input terminals to verify adequate
voltage.
Power meter is wired
Check all CTs and PTs to verify correct connection to the same
improperly.
service, PT polarity, and adequate powering. See the Wiring
Diagrams section for more information.
Power meter address is incorrect. Verify that the meter is correctly addressed (see Setup section).
Power meter baud rate is
Verify that the baud rate of the meter matches that of all other
incorrect.
devices on its communications link (see Setup section).
Communications lines are
Verify the power meter communications connections (see the
improperly connected.
Communications section).
Verify the terminating resistors are properly installed on both ends
of a chain of units. Units in the middle of a chain should not have
a terminator.
Verify the shield ground is connected between all units.