Veris Industries E50F2A Installation Manual page 2

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide
Specifications
(cont.)
ZL0119-0F
Page 2 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
AC
DC**
Ride Through Time
Pulse
Minimum Pulse Width
Alarm Contacts
(E50F2A only)
Communication Port
Weight
IP Degree of Protection
(IEC 60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Mounting Rail
Operating Temperature
Storage Temperature
Humidity Range
Altitude of Operation
Mounting Location
US and Canada
Europe (CE)
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
Agencies: US and Canada
(cULus)
*Not recommended for environments where high harmonic content is present.
** External DC current limiting is required, see fuse recommendations.
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
CONTROL POWER
5 VA max.; 90 V min.;
UL Maximum: 600 V
(347 V
); CE Maximum: 300 V
L-L
L-N
3 W max.; UL and CE: 125 to 300 Vdc
100 msec at 120 Vac
INPUT
Solid-state or mechanical contacts (current less than 1mA)
20 msec
OUTPUT
N.C., static output; (30 Vac/dc, 100 mA max. @ 25 °C, derate 0.56 mA per °C above
25 °C)
2-wire, LON TP/FT-10
MECHANICAL CHARACTERISTICS
0.62 lb (0.28 kg)
IP40 front display; IP20 meter
Back-lit blue LCD
0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) max.
24 to 14 AWG (0.2 to 2.1 mm
)
2
T35 (35 mm) DIN Rail per EN 50022
OPERATING ENVIRONMENT
-30 to 70 °C (-22 to 158 °F)
-40 to 85 °C (-40 to 185 °F)
<95% RH (non-condensing)
3 km max.
Not suitable for wet locations. For indoor use only.
COMPLIANCE INFORMATION
CAT III, Pollution Degree 2;
for distribution systems up to 347 V
L-N
IEC/EN 61010-1
CAT III, Pollution Degree 2;
for distribution systems up to 300 V
L-N
Per UL 508, IEC/EN 61010-1
FCC part 15 Class B, EN 55011/EN 61000 Class B (residential and light industrial)
EN 61000 Class A (heavy industrial)
UL 508 (open type device)/CSA 22.2 No. 14-05
L-N
/ 600 Vac
L-L
TM
0119