Quick Setup Instructions; Pulse Contact Inputs - Veris Industries E50F2A Installation Manual

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide
Quick Setup
Instructions

Pulse Contact Inputs

ZL0119-0F
Page 10 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
These instructions assume the meter is set to factory defaults. If it has been previously configured, check all optional values.
A. To Navigate to the Setup screens:
+
1. Press
+
or
repeatedly until SETUP screen appears.
2. Press
to get to the PASWD screen.
3. Press
to move through the digits. Use the
4. Press
to move to the first Setup screen (S CT)
+
5. Use
+
or
to select the parameter screen you want to set.
6. After you set the parameters you want, use
SETUP).
B. To Enter the CT (Current Transducer) output voltage and CT size ranges:
1. Press
to go to the CT SZ screen and through the digits. Use
value and
2. Press
to accept the value and go back to the S CT screen.
C. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
2. Press
to go to the SYSTM screen. Use
Press
to go back to the S SYS screen.
For full setup instructions, see the configuration instructions on the following pages.
The E50F5A has two inputs with pulse accumulators for solid state or mechanical contacts in other sensors, such as water or gas
flow meters. The E50F2A has one pulse input. These inputs are isolated from the measured circuits. The communication signals,
including the shield terminal, are AC-coupled. Use with contacts that do not require current to remove oxidation.
Pulse Input
Contacts
E50F5A only
~10 k
+
4-10 VDC
nominal
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
+
+
or
buttons to enter your password (the default is 00000).
+
+
or
to select the next Setup screen or
+
or
to select the CT size in amps (default is 100). accept the
+
+
+
or
to select the configuration (see wiring diagrams - default is 3L-1N).
Comm
S
Output
Equivalent
Circuit
Comm
Ground
TM
to exit the Setup screens (return to
0119