Veris Industries E50F2A Installation Manual page 15

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide
UI for Setup
To Setup p. 2 "SPASS"
Back
S CT
Current
Transformer
Back
S SYS
System
Type
Back
S PT
Potential
Transformer
Back
S
V
Sytem
Voltage
Back
S PWR
Sytem
Voltage
To Setup p. 2 "SPLOS"
ZL0119-0F
Page 15 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
CT SZ
--------
100
Next
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L-1n
Next
RATIO
--------
001.00
Next
V LL
--------
00600
Next
MX KW
--------
103.92
Next
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Set Current Transducer:
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System
Reg 130 CTs
Description
3L-1n
40
3
Wye Three Phase: A, B, & C with Neutral (Default).
3L
31
3
Delta Three Phase: A, B & C; no Neutral
2L-1n
12
2
Single Split Phase: A & B with Neutral
2L
11
1
Single Phase: A & B; no Neutral
1L-1n
10
1
Single Phase: A to Neutral
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Wiring Diagrams section. Set this value before
setting the system voltage to establish the proper range of System
Voltage values.
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power,
and as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by "V LN". Note: the meter will reject settings
that are not within the meter's operating range when divided by the PT ratio.
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power Factor
is assumed to be unity. The value of System Power is used to determine
which combinations of pulse weight and duration are valid and will keep up
with the maximum power the meter will see. This value is read only.
Default values are in Bold