Installation Guide
Power Monitoring
E34E
E212445
Z207251-0C
Page 1 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
E34A
Product Overview
The E34 Series Multi-Circuit Meters are designed to measure the current, voltage and energy consumption of up to
14 3-phase circuits with a single board or up to 28 3-phase circuits with a 2-board configuration.
The E34 uses commonly available split-core current sensors with 1/3 V (voltage-mode) outputs to cover a wide
range of loads.
Data is transmitted using an RS-485 Modbus protocol. E34E models also incorporate Ethernet, with support
for BACNet IP, Modbus TCP and SNMP protocols and include BACnet MS/TP serial capability and a sturdy metal
enclosure.
The E34 comes pre-configured for 3-phase loads, but can easily be configured on site to accommodate any
combination of 3-phase, 2-phase and single-phase loads, with or without Neutral current, using the channels
available on the model selected (see table below).
To configure the E34 for operation, use the NetConfig configuration software tool and the E3x Commissioning Guide
on the USB drive provided.
Product Identification
Communication
Option
E34
A = Modbus RTU only
E = Integrated Ethernet with
Modbus, BACnet & SNMP
Number of Meters Supported
E34A
Modbus RTU Only
E34A04
E34A08
E34A14
E34A28
©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
E34 Series
Multi-Circuit Meters
Number of
3-Phase Meters
04 = 4 (3-phase) meters
08 = 8 (3-phase) meters
14 = 14 (3-phase) meters
28 = 28 (3-phase) meters
E34E
Integrated Ethernet
E34E04
E34E08
E34E14
E34E28
TM
Number of Meters
3-Phase
2-Phase
1-Phase
4
6
12
8
12
24
14
21
42
28
42
84