Wiring - Veris Industries E50F2A Installation Manual

Compact power and energy meters with lon tp/ft-10 communication for use only with e683 series rope cts
Table of Contents

Advertisement

E50F2A, E50F5A Installation Guide

Wiring

ZL0119-0F
Page 8 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT terminals are referenced to the meter's neutral and may be at elevated voltages:
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
1. Turn off all power supplying this device and the equipment in which it is
installed before working on the device or equipment.
2. Always use a proerly rated voltage sensing device to confirm that all power
is off.
3. Connect the CT output leads to the meter inputs. The white wire is the X1
lead. The E683x CT has an arrow indicating the source side.
4. Release the clasp on one side of the CT and open it on the hinge.
5. Fit the Rogowski coil around the conductor, bringing the coil ends
together.
6. Lock the coil by turning the ring clockwise as shown in the diagram
at right.
7. Reconnect power to the panel.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
Use System Type 10 (1L + 1n)
N L1
X1
X2
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
Use System Type 12 (2L + 1n)
N
L1
L2
X1
White
Black
X2
X1
White
Black
X2
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
L1 L2
A
B
C
N
X1
White
X1
Black
A
X2
X2
X1
B
X2
X1
C
X2
L1 L2 L3
A
B
C
N
X1
X1
A
X2
X1
X2
B
X2
X1
C
X2
Diagram 2: 1-Phase Line-to-Line 2-Wire
System 1 CT
Use System Type 11 (2L)
White
Black
Diagram 4: 3-Phase 3-Wire 3 CT no PT
Use System Type 31 (3L)
White
Black
White
X1
Black
White
X2
X1
Black
X2
TM
A
B
C
N
X1
A
X2
X1
B
X2
X1
C
X2
A
B
C
N
X1
A
X2
X1
B
X2
X1
C
X2
0119

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50f5a

Table of Contents