NAPCO Gemini GEM-P1632 Programming Instructions Manual page 59

Global panel communicator
Table of Contents

Advertisement

WI897B 8/98
Page 59
Relay Follows Zone
External Relays can be programmed to follow a zone. If values are entered in Time locations, the relay will time out after the
programmed time.
Relay Outputs See Alarm Outputs
Remote Panic See Panic Zone
Report Telco 1; Report Telco 3 (Double or Split Reporting)
Alarms, alarm restores, troubles and trouble restores may be selected individually for each zone. Violation of a zone selected to report
will communicate the code(s) selected for that zone to the central station.
Normally, Report Telco 1 is used to report to the central station. Report Telco 3 is used when certain zones will report to a different
receiver (split reporting); Report Telco 1 and Report Telco 3 are both used on the same zone to report to two receivers successively
(Double Reporting). (Double Reporting requires a successful report to Telco 1 before reporting to Telco 3.) Also see Backup Report
on Telco 2.
Reset Day Zone with Arm/Disarm Only See Day Zone
Reset Relay See Alarm Outputs
Silence All Outputs During Audio Session See Veri-Phone
Single-Digit Format See Data Format
Smoke Detectors
Connect smoke detectors as shown in the diagrams. The "Fire Power" (Terminal 25) is used to reset the smoke detectors.
Two-Wire Smoke Detectors
Two-wire smoke detectors may only be used only on Zones 7 and 8. Up to 10 compatible 2-wire smoke detectors may be wired to
each zone. In Residential applications, program Pulse Burg Output. Program Disable Fire Reset in the applicable area(s).
Zones 7 and 8 have been designed so they can be easily configured as 2-wire smoke detector zones by means of jumpers (JP3)
located above Terminal 21.
1. Program Zones 7 and/or 8 for 2-Wire Smoke Detectors and Fire.
2. If Zone 7 is selected as a 2-Wire Fire Zone, move the left jumper on JP3 from the top two pins (BURG) to the bottom two pins
(2WF).
3. Similarly, if Zone 8 is selected as a 2-Wire Fire Zone, move the right jumper on JP3 from the top two pins (BURG) to the bottom two
pins (2WF).
4. Connect 2-wire smoke detectors to Zones 7 and/or 8 as shown in the GEM-P1632 Installation Instructions (WI808).
Four-Wire Smokes
If installing 4-wire smokes, subtract smoke-detector alarm current from available standby current. See COMPATIBLE UL-LISTED
DEVICES.
Wire 4-wire smokes as shown in the GEM-P1632 Installation Instructions (WI808). Program each zone for Fire. Also program zones
for Pulse Burglary Output, and Disable Fire Reset in the applicable area(s) (System Options). If they are of the self-resetting type,
4-wire smokes may be powered from Terminals 25 and 6.