NAPCO Gemini GEM-P1632 Programming Instructions Manual page 56

Global panel communicator
Table of Contents

Advertisement

Page 56
Keypad Features
The following programmed system features will activate only if they have also been enabled at the keypad.
Ambush
Easy Arming
Access Control
Keypad (Police) Panic
Keypad Auxiliary Panic
Keypad Fire Panic
Keypad Panic See Panic Zone
Keypad Sounder on Alarm
If a programmed zone goes into alarm, the keypad sounder will activate and will remain activated until the
or the system is disarmed.
Keypad Tamper See Tamper
Keyswitch Arming
The area will arm/disarm when the programmed zone is momentarily shorted (momentary keyswitch). To supervise the keyswitch,
program the zone for Day Zone on Open.
Line-Reversal Module, M278
The Line-Reversal Module allows the panel to be monitored by a central station through leased lines. On alarm, the module reverses
normal line-voltage polarity. For details, refer to the instructions furnished with the module.
Loop Response (750mS required for UL installations)
Loop response is the amount of time in milliseconds (mS) that a normally-closed circuit must remain open, or a normally-open circuit
must remain closed, to trigger an alarm. The slower the loop response, the more immune the system will be to intermittents
("swingers"). Loop response times for Zones 1 through 8 are programmed into the control panel; Zones 9-16 with "Zone Doubling"
enabled have loop responses the same as their respective 1-8 zones; those for Zones 9 through 32 loop responses are selected in
the respective keypad configuration mode or expansion module jumper. (Refer to keypad instructions and EZM Installation
Instructions.)
Selectable loop-response times for Zones 1–8 are:
750mS (.75 sec.): The slowest loop-response time, recommended for use with magnetic contacts, window foil, etc. Unless
programmed otherwise, loop-response time will be 750mS for all zones.
50mS (.05 sec.): Used for momentary Panic Buttons and area-protection devices, such as photoelectric eyes, passive infrared
sensors, floor mats, etc.
10mS (.01 sec.): An extremely fast loop response used primarily for window bugs.
Low Battery (Required for UL Mercantile installations)
A low-battery system trouble will annunciate at the keypad when the battery terminal voltage drops below normal. This condition may
signal a local sounding device, report to a central station (program Panel Low Bat Report Code), or both. If a battery is installed and
low terminal voltage is detected, a restore will not occur until the battery is recharged to its specified level and passes a dynamic test.
The dynamic test may be initiated manually by pressing the
panel.
In wireless installations, when displaying rf transmitter status, a "LoBatt" indication denotes a low-battery condition at the transmitter.
Memory Failure
A User or Dealer Memory error will cause the sounder to pulse, the "
 
!   
" or "
"SYS/TRBL" reminder). Activate RESET SYSTEM TROUBLE to manually reset the system trouble. A Memory Failure can be
programmed to activate an alarm output and/or report using its associated system Report Code.
GEM-P1632 Programming Instructions

button, or it will be initiated automatically, every four hours, by the

  
". Press the
button to silence the sounder ("
" reminder to flash, and the display to read "
  
" will display, along with the
NAPCO Security Systems
WI897B 8/98

button is pressed
  

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents