INTRODUCTION
The StarLink
Commercial / Residential Fire and Burglary
alarm capture radio communicators are fully supervised,
wireless digital two-way subscriber units supported by an
extensive nationwide wireless network.
compatible with most 12VDC alarm control panels (always
adhere to the documentation provided by the control panel
manufacturer). Model SLE-LTEV-CFB is compatible with
most 12 or 24VDC control panels. All can function as a
backup to existing telephone lines, or as sole path primary
communicators. In backup mode, all units will automatical-
ly switch the communication channel from the telephone
line to the network when telephone line trouble is detected.
See WI2140 for programming information.
The SLE-LTE Series radios use data-capture technology
that captures the alarm report from the control panel and
transmits the alarm signals to the SLE Control Center; the
alarm signals are then forwarded to ANY central station via
Contact ID or Sur-Gard System II or Sur-Gard System V
central station receivers via TCP/IP using standard line
security. The SLE Control Center reports a trouble signal
in the event that the network does not receive the expected
supervision signal from the wireless communicator.
For Commercial Burglary installations, under the
STARLINK RADIO REPORTING PATH
The diagram below shows the transmission path of a
signal from the StarLink radio to the central station.
1. Signal from a Control Panel.
2. StarLink radio receives the signal transmission
(from the TIP an RING wires); sends RF signal
through the network operator.
3. Network Operator, part of the vendor system, a
section of the cellular spectrum.
4. SLE Control Center, receives and routes data.
5. Central Station.
StarLink
Radio
Control
Panel
(1)
(5)
CENTRAL
STATION
StarLink
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
StarLink™ SLE-LTE Commercial Series
INSTALLATION INSTRUCTIONS
All models are
(
(
(
(
(
(
(
)
(
)
(
)
(
)
(2)
(3)
Network
Operator
(4)
UL Classified StarLink Network
Operations Center
Alarm Communicators
armed condition, any loss of communication must be
treated as a Burglary Alarm at the Central Station.
The following models are available:
SLE-LTEV-CFB-PS: Commercial / Residential Fire and
Burglary Radio in red metal housing with SLE-ULPS-R
power supply and 16.5V / 20VA transformer mounted
inside housing
SLE-LTEV-CB-TF:
and Residential Fire Radio in white metal housing with
SLE-ULPS-R power supply and TRF12/T123 plug-in
16.5V / 20VA transformer
SLE-LTEV-CFB: Commercial / Residential Fire and Bur-
glary in red metal housing. Powered directly from control
panel (no power supply, no transformer, rated 12/24VDC
input)
SLE-LTEV-CB: Commercial / Residential Burglary and
Residential Fire Radio in white metal housing. Powered
directly from control panel (no power supply, no trans-
former)
The following features are included with models that include
a SLE-ULPS-R power supply:
 Power limited output to the StarLink radio PC board 12V
input terminals
 Battery connection red and black flying leads
 Monitored battery charging and Active battery test circuits
 StarLink radio trouble input (from StarLink radio PC board
PGM1 terminal to detect StarLink radio trouble)
 Requires a sealed lead acid min 4AH / max 7AH battery
for minimum 24-hour standby time (max charge current
200mA).
 Trouble relay output (C, N/O and N/C terminals) to wire
to a panel zone dedicated to "LTE Trouble" (dry con-
tacts).
ground
 Green AC ON LED visible from the exterior housing
 Yellow TROUBLE LED on PC board. Flashes signify:
One flash: AC fail / brownout (2 hour delay)
Two flashes: Low battery
Three flashes: Charging circuit trouble
)
)
)
)
)
)
Four flashes: StarLink radio trouble
The housing-mounted transformer (when provided) is mount-
AGENCY LISTINGS
 UL 864 Standard For Control Units and Accessories For
Fire Alarm Systems, 10th Edition
 UL 1610 Standard For Central-Station Burglar-Alarm Units
 UL 985 Standard For Household Fire Warning System Units
 UL 1023 Standard For Household Burglar-Alarm System
Units
LTEV models are Verizon
Commercial / Residential Burglary
Remove jumper "J2" to isolate common from
®
Network Certified
WI2226ALF 8/18
1

Advertisement

Table of Contents
loading

Summary of Contents for NAPCO StarLink SLE-LTE Commercial Series

  • Page 1 For Technical Service, (800) 645-9440 or visit us at http://tech.napcosecurity.com/ (Note: Technical Service is for security professionals only) Publicly traded on NASDAQ Symbol: NSSC © NAPCO 2018 WI2226ALF 8/18 INTRODUCTION armed condition, any loss of communication must be ™ treated as a Burglary Alarm at the Central Station.
  • Page 2: Additional Components

     Input Current for SLE-LTEV-CFB: 10V = 90mA, 12V = Requires connection to either the model NAPCO 71mA, 25V = 68mA, with peak RF transmission current TRF12/T123 (16.5V / 20VA) external plug-in transformer of 200mA.
  • Page 3: Terminal Descriptions

    TERMINAL DESCRIPTIONS triggered with N/O or N/C relay contacts. Wire the common ground terminal GND (terminal TB8) to the Configure all inputs and outputs using the Manage- relay common. In Burglary applications, when used ment Center screen (located at www.napconoc.com). as arm/disarm status input, a low indicates "armed"...
  • Page 4: Supplying Power

    ality; requires a restart (full power down and full power up sequence) to restore operation  8 Blinks: Telco Line Cut (this is not the DACT inter- connect to the radio) RED DIAGNOSTIC LED Labeled "D7", this LED is located in the middle of the PC board.
  • Page 5: Network Coverage

     Generally, high locations are best. DO NOT mount radio See page 12 for GEMC-F8ZCPIM wiring. Should be programmed on Napco control panels as Day Zone, but in basements or below grade as unpredictable perfor- be programmed to sound locally and NOT activate the mance may result.
  • Page 6: Step 5: Signal Verification

    StarLink radio have been properly received by your central station before leaving the premises. Keypad Emergency Alarm* E140 Opening* E401 NAPCO CONTROL PANEL PROGRAMMING Closing* R401 To program the central station receiver reporting format, A.C. Trouble* E301 use PCD-Windows Quickloader download software. Open...
  • Page 7 the previous page. panel must trigger an output to activate the StarLink radio Note: These event codes and zone numbers can be to report this line cut fault to the central station. Program changed from the Management Center screen (located at the control panel for telephone supervision.
  • Page 8 (Commercial Fire and Commercial Burglary) SLELTEV-CFB-PS Wiring Diagram SLELTEV-CFB-PS Yellow Green AC Trouble ON LED PC Board All connections are power limited except AC Mains, Telco and battery terminals Power Supply (SLE-ULPS-R) Terminals 14-17: No connections permitted . Relay con- Note: Connect IN2 to a tacts rated max 30VDC,...
  • Page 9 (Commercial Burglary) SLE-LTEV-CB-TF Wiring Diagram SLE-LTEV-CB-TF Yellow Green AC Trouble PC Board ON LED All connections are power limited except AC Mains, Telco and battery terminals Power Supply (SLE-ULPS-R) Terminals 14-17: No connections permitted. Relay con- Note: Connect IN2 to a tacts rated panel output used for max 30VDC,...
  • Page 10 Wiring Diagram for PRIMARY Reporting Configuration Generic Control Panels (Use when telephone line is NOT available) (CONTROL PANEL HOUSING) CONTROL PANEL PC BOARD Transformer 12VDC (–) AUX POWER TBL INPUT (TIP) (–) (RING) Optional: When Power Supply SLE-ULPS-R is not used, connect Panel Aux Power to StarLink terminals 1 and 2 (observing polarity)
  • Page 11 Wiring Diagram for BACKUP Reporting Configuration Generic Control Panels Transformer (CONTROL PANEL HOUSING) CONTROL PANEL PC BOARD TO TELCO RING RJ31X 12VDC TELCO (TELCO) (PHONE) AUX POWER OUTPUT (TIP) (TIP) (–) (RING) (RING) Telco TBL Optional: When Power Supply Output SLE-ULPS-R is not used, HOME ZONE (+)
  • Page 12 Wiring Diagram for PRIMARY Reporting Configuration GEMC-32, GEMC-96, GEMC-128 and GEMC-255 Control Panels (Use when telephone line is NOT available) (CONTROL PANEL HOUSING) GEMC Control Panel PC Board RJ31X RING RJ31X RING SEE WIRING DIAGRAM AND WI FOR ADDITIONAL INFORMATION MONITOR ZONE (+) DEDICATED TO...
  • Page 13 Wiring Diagram for PRIMARY Reporting Configuration GEMC-32, GEMC-96, GEMC-128 and GEMC-255 Control Panels (Use when telephone line is NOT available) (CONTROL PANEL HOUSING) GEMC Control Panel PC Board RJ31X RING RJ31X RING SEE WIRING DIAGRAM AND WI FOR ADDITIONAL INFORMATION ZONE (+) DEDICATED TO SUPER-...
  • Page 14 Wiring Diagram for BACKUP Reporting Configuration GEM-X255 / GEM-P9600 / GEM-P3200 Control Panels (CONTROL PANEL HOUSING) Control Panel PC Board 16VAC Transformer Summary of connections:  RJ31X RED to StarLink module 10 TO TELCO  RJ31X GREEN to StarLink module 11 ...
  • Page 15 Wiring Diagram for PRIMARY Reporting Configuration GEM-816 / GEM-P1632 / GEM-P1664 Control Panels (Use when telephone line is NOT available) Control Panel PC Board TELCO PHONE RING TIP RING 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Note: Connect IN2 to a ZONE (+)
  • Page 16 Wiring Diagram for BACKUP Reporting Configuration GEM-816 / GEM-P1632 / GEM-P1664, Freedom F-64 Control Panels 16VAC (CONTROL PANEL HOUSING) Transformer Control Panel PC Board Summary of connections:  RJ31X RED to StarLink module 10 TO TELCO  RJ31X GREEN to StarLink module 11 Optional: When Power Supply SLE-ULPS-R is not ...
  • Page 17 ALARM ALARM ALARM Linecut state of panel for Napco panels when used Linecut for DACT intercon- with local download cable). nection wiring to the radio reports via an input on radio. Requires two 10K EOLRs. Three off nor-...
  • Page 18 Tamper Switch Mounting Instructions WIRING THE TAMPER SWITCHES (REQUIRED FOR UL COMMERCIAL BURGLARY) Before installation and wiring, the tamper switches (part GEM- Tamperkit) are normally open devices; when placed into the circuit and into operation, they are normally closed devic- Tamper switches protect against the opening of the radio cabi- net door or the removal of the radio enclosure from the wall or other mounting surface.
  • Page 19 UL LISTED ELECTRICAL PULL BOX WITH LISTED OUTLET BOX AND NON-SWITCHED RECEPTACLE ON DEDICATED FIRE ALARM SYSTEM BRANCH CIRCUIT CONDUIT TRANSFORMER OUTPUT WIRING UL LISTED PULL BOX UL LISTED NAPCO TRF12/T123 TRANSFORMER FOR WALL CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX...
  • Page 20: Napco Limited Warranty

    A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. it is possible for the system to fail to perform as expected. NAPCO does not ADDITIONALLY, THIS WARRANTY IS IN LIEU OF ALL OTHER represent that the product/system may not be compromised or OBLIGATIONS OR LIABILITIES ON THE PART OF NAPCO.