NAPCO Gemini GEM-P1632 Programming Instructions Manual page 55

Global panel communicator
Table of Contents

Advertisement

WI897B 8/98
Page 55

Fire; Keypad Fire
Any zone may be programmed for Fire. Connect normally-open devices across a Fire Zone. (The EOL2.2K end-of-line resistor must
 
be installed.) A short across the zone will cause a fire alarm, which will be indicated at the keypad by a "
" LCD display and pulsing
 


sounder. An open circuit on the Fire Zone will identify a trouble and cause flashing "
" LCD display and pulsing sounder after a
10-second delay. The sounder may be silenced by pressing the
button. The LED will go off within 30 seconds after reset if the
alarm or trouble is cleared. For Smoke-Detector Reset, see Alarm Outputs.
A fire condition that has not been restored will cause the zone number and description to scroll. To reset (acknowledge) the condition,
enter a valid code, then press the
button. If Keypad Fire is programmed, pressing both the
and
buttons at the
 
same time will sound a fire panic alarm and display "
" at the keypad. The Keypad Fire function is supplementary
to the hardwired zones. Note: This feature shall not be considered a substitute for listed manual initiating devices.

Include Selective/Group Bypass In Conditional Closing/Status See Closing Report; Interior Zones by Area; Interior Normally

Bypassed; Auto Interior Bypass
Removal of a programmed group of interior zones from the system will permit freedom of movement throughout the premises but still
afford protection from intrusion through armed perimeter zones. Pressing the
button prior to arming will select the Interior

Zones, then arm to bypass. The next time the control panel is disarmed, all bypassed zones will automatically revert to non-bypassed
 
(disarmed) zones. When the
button is pressed, the "
" reminder will come on.
The bypassed zones may be displayed on the keypad (see GEM-RP1CAe2 FUNCTION MODE).
 
If Interior Normally Bypassed is selected, all Interior Zones will always be inactive. The "
" reminder will always display,

indicating that only partial protection will be provided upon arming. To temporarily restore interior protection, press the
button;
 
the "
" reminder will go out upon arming, denoting full protection, however Interior Zones will once again be bypassed the
next time the panel is disarmed.
If "Auto Interior Bypass" is programmed, all Interior Zones will automatically provide protection if the Exit/Entry doors are opened
during exit delay. (Note: Interior Normally Bypassed must be programmed.) If the
button is pressed while armed, exit delay will
restart and Exit/Entry doors may be opened to permit someone to exit (while others remain on premises) without causing an alarm.
Jumpers (Refer to Wiring Diagram for UL configuration)
JP1: Keypad Configuration Jumper (top-right corner, above micro shield) is installed across top and center pins for normal operation.
When configuring GEM-RP1CAe2 keypads, move jumper across center and lower pins.
JP3: 2-Wire Fire jumpers. Select Zones 7 and/or 8 for use as either 2-Wire Fire Zones or Burglary Zones. Note: If customizing a
single-area default program, Zone 8 is configured as a 2-Wire Fire Zone. In a two-area default program, Zones 7 and 8 are configured
as 2-Wire Fire Zones common to both areas; be sure to move JP7 Zone-7 jumper to the 2-WF position (see Wiring Diagram).
GEM-RP1CAe2 Keypad Jumpers
Refer to label LA1374 on the circuit board fishpaper for jumper locations and a summary of settings.
JP1: Cut to enable Keypad Tamper.
W1 & W3: Cut both to disable touch pad backlighting.
W2: Cut to disable LCD backlighting.
GEM-RP2ASe2 Keypad Jumpers
Refer to label LA1390 on the circuit board fishpaper for jumper locations and a summary of settings. See Section 3: Configuring the
GEM-RP2ASe2 Keypad for jumper selection.
Key Fob Transmitters
Aux. Output Chirp on Key-Fob Arming
Don't Clear Aux. Relay with Arm/Disarm
Aux. Output Chirp on Key-Fob Arming will cause a 1-second chirp to sound on arming and a 2-second chirp on disarming. Use the
steady output of a siren driver. Do not use a voice siren driver.
Programming a "C as the Key-Fob Aux-1 or Aux-2 option will provide the ability to toggle the Aux. Relay on or off. If there is an Aux.
Relay timeout programmed, it will follow this timeout unless toggled off by the key fob. To provide key-fob-only control, program no
timeout. Program Don't Clear Aux. Relay with Arm/Disarm to prevent a disarm from resetting the Aux. Relay. Key-fob users can report
openings and closings. Key fobs 1–8 report as Users 25–32, respectively.
Keypad Access see Access Control
Keypad Area Assignments
In multiple-area systems, assign an Area Number ("1" or "2") to each keypad. Note that each address comprises 2 nibbles; enter the
Area Number in the right nibble.
NAPCO Security Systems
GEM-P1632 Programming Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents