WI897B 8/98
Page 53
Disable Answering Machine Download See Callback-Method Download
Disable Auto-Reset on Day Zone See Day Zone
Disable Auto Status
  
Non 24-Hour Zones that are open (or shorted) normally display "
" (while disarmed) followed by the zone number(s) and
 
description(s). In high-security applications, program Disable Auto Status. Unsecured zones will then be indicated by a "
display. Status may be displayed manually using the DISPLAY STATUS function, however a valid user code will be required.
Disable Auto-Unbypass on Disarming
Normally, manually bypassed zones revert to active (disarmed) zones on disarming. Select this feature to maintain bypassed zones on
disarming until manually unbypassed.
Disable Call Waiting (touch-tone® Dialing Only)
A digital communicator connected to a telephone line with Call Waiting may be disrupted by this feature. However, most lines with Call
Waiting also have Selective Call Waiting, which permits the feature to be turned off by dialing a "*70" just before the telephone number.
A "*" will be dialed by programming a "B".
If the installation has the Call Waiting feature, be sure that it also has Selective Call Waiting, and confirm the disable code with the
telephone company. Then program this code ("B70") directly before the phone numbers (after dial-tone detection or pre-dial delay) in
the telephone-number locations. See Telephone Numbers.
Caution: Should the user cancel his Call Waiting service, the communicator will dial a wrong number unless the phone number is
corrected.
Disable Callback Download See Callback-Method Download


Disable Code Required for Easy Bypass See Selective Bypass (Do not program in UL Installations)
Disable Fire Reset (by Area)
Normally, pressing the
button will momentarily remove power to the smoke detectors. If "Disable Fire Reset" is selected for any
area, the
button will no longer activate the Reset Output so that the integrity of the smoke detector's Alarm Memory feature
(LED indication) will be maintained. Also see Alarm Outputs; Smoke Detectors.
Disable Function-Mode Download See Callback-Method Download
Disable Openings/Closings
Provides the flexibility of disabling openings and/or closings from any area(s).
Disable Wait-for-Handshake/Kissoff
Causes data transmission to start immediately after the telephone number.
Disable Wait-for-Silence (Pager Format)
Causes data transmission to start immediately after the pager telephone number.
Double Reporting See Report Telco 3
"E" Lugs (E5, E15, E19)
E5 - Lug E5 is used for Line Seizure. It is normally at 12V and when the telephone line is seized it goes to approximately 1V DC.
E15 - Lug E15 is used for Armed State. It is normally at 12V and when the system is armed it goes to approximately 1V DC.
E19 - Lug E19 is the Listen in Lug. It is an input and when it is forced low the panel will silence the keypad sounder and bell outputs so
that the Ver-phone can listen to activity at the residence. See Veri-Phone (WI783): Silence All Outputs During Audio Session.Use
Napco Part No. WL1 for field wiring.

Easy Arming
Permits quick arming by simply pressing the
button. Each keypad may be individually programmed for Easy Arming (see Keypad
Features). Disarming still requires entry of a valid user code. Do not program Easy Arming in UL installations. If closings are reported,
Easy Arming will report as User 99.