INTRODUCTION
The SLE-LTEVI-FIRE and SLE-LTEAI-FIRE Dual-Path
Alarm Communicators are specifically designed to interface
with FACP (Fire Alarm Control Panels) and to comply with
UL 864. The communicators are equipped with two dry
relays, one for a trouble output and one for an auxiliary out-
put. The units are also equipped with four supervised in-
puts to report a Fire Alarm, a Fire Trouble, a Water Flow
Alarm and a Supervisory Alarm, each triggered from the
N/O and Common terminals of the associated FACP output
relays. These communicators are for use as the primary
means of communication with the central station and do not
have backup mode capability. Dual Path Communicators
can also be utilized as a Sole Path Cell Communicator. No
POTS (Telco Line) connection permitted.
When connected to a FACP with one or two standard RJ-
45 telephone inputs, the SLE-LTEVI-FIRE and SLE-LTEAI
-FIRE provide two RJ-45 outputs to satisfy both telephone
inputs. The primary RJ-45 output is supervised and reports
a trouble to the central station upon any open or short on
the primary RJ-45 wires that prevent reporting. The sec-
ondary telephone line is supervised by the FACP; when a
line fault is detected, a trouble is reported to the central
station through the primary telephone line.
The SLE-LTEVI-FIRE and SLE-LTEAI-FIRE are compati-
ble with most 12 or 24VDC alarm control panels (always
adhere to the documentation provided by the control panel
manufacturer). Mount to a single-, dual-, or three-gang
electrical box and route the wires through the back knock-
out(s), or as specified by local codes. See WI2140 for pro-
gramming information.
The SLE-LTEVI-FIRE and SLE-LTEAI-FIRE communica-
tors use proprietary data-capture technology that captures
the alarm report from the control panel and transmits the
alarm signals to the SLE Control Center; the alarm signals
are then forwarded to ANY central station via Contact ID or
4/2 via DACT from the NOC or Sur-Gard System II, Sur-
Gard System V, Bosch D6100IPV6 or Bosch D6600 Re-
ceiver (with ITS-D6686 Ethernet Adapter) via TCP/IP using
standard line security. The SLE Control Center reports a
trouble signal in the event that the network does not re-
ceive the expected supervision signal from the wireless
communicator. In addition, the SLE-LTEVI-FIRE and SLE-
LTEAI-FIRE are powered directly from the control
panel. Note: UL Listed for UL 1076 APOU Proprietary
Alarm Systems and UL 365 APAW Police Connect when
reporting to a UL Listed Central Station Receiver Listed for
UL 1076 APOU Proprietary Alarm Systems or UL 365
APAW Police Connect, respectively.
Bosch D6600 or D6100IPV6 for UL1076 and UL365 appli-
cations.
*For Commercial Fire installations, a UL Listed Fire Alarm regulated power
supply or FACP regulated auxiliary output is required.
StarLink
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions
StarLink™ Commercial
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE
Dual-Path Alarm Communicators
INSTALLATION INSTRUCTIONS
For TCP/IP only
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE - Commercial / Resi-
dential Fire LTE Network Compatible alarm capture
Communicator. SIM card included. Red plastic enclo-
sure. Rated nominal 12/24VDC input.
ADDITIONAL COMPONENTS
In addition to the SLE-LTEVI-FIRE and SLE-LTEAI-FIRE
listed above, the following sub-assemblies are available:
SLE-WIFI-MODULE - Allows your Napco StarLink
to connect to the Internet by means of a wireless (Wi-Fi)
link, eliminating a wired Ethernet cable connection.
Note: 7AH battery required when using the SLE-
WIFI-MODULE. For more information, see WI2191.
SLE-DLCBL - Download Cable, 6 feet.
SLE-ANTEXT30 - Extended antenna with 30 feet of cable
SLE-ANTEXT50 - Extended antenna with 50 feet of cable
SLE-ANTEXT75 - Extended antenna with 75 feet of cable
SLE-ANTEXT100 - Extended antenna with 100 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in-
structions. Note: Antennas are not Listed by UL.
SPECIFICATIONS
Electrical Ratings for +12V / 24V (powered by the con-
trol panel)*
Input Voltage: 10-25VDC regulated (power-limited out-
put from Listed control panel Aux/Remote Fire Power).
Input Current:
10VDC standby: 162mA
12VDC standby: 125mA
15VDC standby: 110mA
24VDC standby: 100mA
25VDC standby: 100mA
Wi-Fi Module: (Optional) Add 40mA to the above.
(With peak RF transmission current of 325mA).
Electrical Ratings for the IN 1 Fire Input:
Input Voltage: 9-25VDC.
Maximum Input Current: Up to 2mA from FACP NAC
circuit
Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:
(Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)
Maximum Loop Voltage: 25VDC input.
Maximum Loop Current: 1.7mA
AGENCY LISTINGS
 UL 864 Standard For Control Units and Accessories For Fire Alarm
Systems, 10th Edition
 UL 1610 Standard For Central-Station Burglar-Alarm Units
 UL 985 Standard For Household Fire Warning System Units
 UL 1023 Standard For Household Burglar-Alarm System Units
 UL 1076 APOU Proprietary Alarm Systems
 UL 365 APAW Police Connect
 NYC Fire Dept. Certificate of Approval #6317 & 6318
WI2326E.bLF 11/20
device
1

Advertisement

loading

Summary of Contents for NAPCO StarLink SLE-LTEVI-FIRE

  • Page 1 Alarm and a Supervisory Alarm, each triggered from the ™ SLE-WIFI-MODULE - Allows your Napco StarLink device N/O and Common terminals of the associated FACP output to connect to the Internet by means of a wireless (Wi-Fi) relays.
  • Page 2 End of Line Resistor (EOLR) Value: 10K configured with the central station telephone num-  ber and correct reporting formats and codes. For Electrical Ratings for PGM3 Output: more information, WI2140 located Open Collector Output: Maximum Voltage 25VDC.  www.NapcoNOC.com. Maximum PGM Sink Current: 50mA (up to 15VDC), ...
  • Page 3  2 Blinks: Battery trouble  3 Blinks: Alarm report Failed to Communicate (will restore only when the radio path is restored)  4 Blinks: RF trouble (antenna connection or cellu- lar registration)  5 Blinks: Radio poll or check-in failure (radio and/or RED DIAGNOSTIC LED (Labeled "D7") Ethernet).
  • Page 4 Fast Flash = No IP connection (occurs just after The SLE series radios are compatible with 4/2 Pulse Dial- power on while trying to obtain a DHCP address) ing formats with 10pps, 20pps, and 40pps with and with- Slow Flashing: out checksum, either 1400Hz or 2300Hz handshake / kissoff.
  • Page 5 IN 1 CO (Carbon Monoxide) E162 cated to monitoring the radio status. Should be pro- Medical Alarm* E100 grammed on Napco GEMC control panels as Monitor or Supervisory Zone. 24 hour Aux. Alarm* E150  TELCO PRIMARY to FACP Telco 1 RJ-45 socket.
  • Page 6 The radio must also report this trouble to the central station. different from that to which the receiver is connected; 4. With NAPCO GEMC series control panels, wire the zone as Consult the dealer or an experienced radio/TV technician indicated in the wiring diagrams further in this manual.
  • Page 7 on site during any reprogramming of the radio or control ble signal shall be sent to Central Station within 5 panel and must perform / re-perform acceptance testing. minutes of failure by the remained active channel. To perform a download or update the radio firmware, jump- d.
  • Page 8 Wiring Diagram for Generic FACPs without TELCO RJ Sockets (CONTROL PANEL HOUSING) F A C P P C B O A R D Optional: Use 12 or 24VDC Listed regulated power supply*. Note: Common radio ground and FACP ground. AUX / REMOTE SECONDARY TELCO PRIMARY TELCO FIRE PWR...
  • Page 9 Wiring Diagram for Generic FACPs with TELCO RJ Sockets (CONTROL PANEL HOUSING) F A C P P C B O A R D Optional: Use 12 or 24VDC Listed regulated power supply*. Note: Common radio ground and FACP ground. AUX / REMOTE FIRE PWR (‒) TELCO RJ...
  • Page 10 Wiring Diagram for FACP Relay Trigger Input Reporting (CONTROL PANEL HOUSING) CONTROL PANEL PC BOARD Aux Power: Regulated 12/24VDC or optionally use 12 or 24VDC regulated Listed power supply*. Note: NORMALLY WATER FLOW SUPERVISORY ENERGIZED FIRE ALARM Common radio ground and ALARM ALARM FIRE TROUBLE...
  • Page 11 Wiring Diagram for GEMC-32, GEMC-96, GEMC-128 and GEMC-255 Control Panels (CONTROL PANEL HOUSING) Requires all 8 wires in the RJ-45 cable GEMC Control Panel PC Board AUX / REMOTE FIRE PWR Or use a 12V/24V UL Listed monitored power supply* TO MONITOR ZONE (+) FACP ZONE OPTIONAL...
  • Page 12 This page intentionally left blank. ™ StarLink SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions...
  • Page 13 Housing Template (1:1 Scale) ™ StarLink SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions...
  • Page 14 This page intentionally left blank. ™ StarLink SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions...
  • Page 15 The following wiring and programming method allows an existing FACP to use its two telephone connections (primary and secondary) for supervision and central station reporting through the StarLink SLE-LTEVI-FIRE radio. By removing the JP2 shunt and enabling the feature "Tip/Ring Wiring Fault Report", when any radio trouble is detected, the StarLink radio will remove voltage from the secondary telephone output, triggering the FACP to locally annunciate the Telco trouble and report the trouble to the central station.
  • Page 16: Napco Limited Warranty