Sylk Bus Cable Specification; Connection Drawings - Honeywell ComfortPoint Open CPO-VAV2A Installation Instructions Manual

Table of Contents

Advertisement

CABLING
Cable lengths and cross sectional areas
Signal type
Cross-sectional
Less than or
equal to 300 Ft.
(100m)
Power
Less than or
supply (24
equal to 16
VAC)
AWG (Greater
than or equal
to 1.5 mm
)
2
Low current
Less than or equal to 20 AWG (Greater than or
signals
equal to 0.5 mm
1
1.E.g. for 0-10 VDC input, NTC20K, PT1000, dry
contact, 0-10 VDC output.
Attention
The maximum length of a signal cable with 24
VAC supply is 550 ft. (170 m). The max. length of
a two-wire, 0-10 Vdc signal cable is 1300 ft. (400
m). The secondary side of the transformer must
not be connected to earth ground.
Installing a fuse on the secondary side of the
transformer is recommended to protect the
devices against incorrect wiring.
MS/TP cable specification
Use Belden 9841 or Equivalent cable with the following
specifications
An MSTP EIA-485 network shall use shielded, twisted-pair
cable with characteristic impedance between 100 and 130
ohms.
Distributed capacitance between conductors shall be less
than 100 pF per meter (30 pF per foot).
Distributed capacitance between conductors and shield
shall be less that 200 pF per meter (60 pF per foot).
Foil or braided shields are acceptable.
The maximum recommended length of an MS/TP segment
is 1000 meters.

Sylk Bus cable specification

Polarity insensitive
Can use daisy chain wiring for multiple Sylk devices. If
wire size is too thick for two wires in the terminal, use
pigtails.
EN1B-0022 IE10 R0717
Less than or
Less than or
equal to 500 ft.
equal to 1300 ft.
(170 m)
(400 m)
Less than or
-
equal to 14
AWG (Greater
than or equal to
)
2
Recommended maximum distance
from controller to any Sylk device
Quantity
Single twisted pair, non-
and type of
shielded, stranded or solid
device
18-22 AWG
3 wall
500 ft
modules,
(150 m)
any type

Connection drawings

This section describes example connection drawings of the
CPO-VAV2A controller with:
MS/TP bus
Sylk bus
24 VAC power, and IO connection
12
Standard
thermostat wire, (non-
twisted), shielded or
nonshielded, stranded or
solid
24 AWG
18-24 AWG
400 ft
100 ft
(120 m)
(30 m)

Hide quick links: