MODEL 50 CONTROLLER – USER GUIDE
TM
NOTE
Factory out CIPer Model 50 Controller
The Factory out CIPer Model 50 Controller comes with WEBs N4.4 versions, which prevents the version
conflict during commissioning between engineering tool and controller.
The introduction of this basic firmware became necessary because the CIPer Model 50 controller cannot
downgraded in terms of the firmware. The base firmware does not allow to start a station and therefore it
must be upgraded to the appropriate firmware version using the Commissioning Wizard.
Before performing CIPer 50 controller rstoring process, make sure to copy clean dist file in the
C:\Honeywell\WEBStation-N4-4.x.x.xxx\cleanDist folder.
Steps to restore CIPer Model 50 Controller:
1.
Connect and enter login details of the CIPer Model 50 platform.
NOTE
Users must keep a record of login credentials details for the CIPer Model 50 platform.
2.
Select Distribution File Installer.
3.
Select the file clean-dist-1-honeywell-nxubc.dist from the list and click the Install
.
Wait for the installation to complete.
After the installation has been completed, the CIPer Model 50 controller will disconnect and reboot.
The default platform passphrase will be active after reboot, enter default login/password for the
o
platform will be active after a reboot. After entering logging credentials Licenses and Certificates
and TCP IP Address Settings will retain.
This action will delete all the modules, station and station data will be erased.
o
Now the Firmware is retained.
o
4.
Click Close after completing the installation.