CIPer
MODEL 50 CONTROLLER – USER GUIDE
TM
Combined network switching & separated networks
Optionally separating networks and switching functionality can be combined.
This allows to have one (or more) controllers connected to the customer intranet, and all other controllers residing
in a closed BMS network.
A typical application is the supervisory controller(s) accessible from the customer intranet, and the room
controllers residing in a closed network, and thus being not directly accessible from the customer intranet.

Front USB/Ethernet interface

All details regarding installation and commissioning of the CIPer Model 50 can be found within the Installation &
Commissioning Instructions – 31-00233.
All models of the CIPer Model 50 controller are equipped with a USB 2.0 Device interface at the front, which is an
Ethernet over the USB connection.
The permanent IP address of this USB interface is 192.168.255.241.
This interface allows connection of WEBs N4 for programming and operation, and web browsers or 3
party touch
rd
panels.
If your WEBs N4 PC or your web browser does not connect to this USB interface, the Windows driver may be
missing. In this case, please see Appendix chapters USB Driver Installation for Windows 7, USB Driver Installation
for Windows 8, and USB Driver Installation for Windows 10 installation for WINDOWS 7/8/10".
19
31-00198-03