11.4 Connecting the
control medium
Important:
Connect the control medium lines
tension-free and without any bends
or knots!
Use appropriate connectors
according to the application.
Thread size of the control medium
connectors: G1/8
Control function
1
Normally closed (NC)
2
Normally open (NO)
3
Double acting (DA)
For connectors 2 / 4 see pictures above
Connector 2
Control
function 1
Connector 4
Connector 2
Control
function 2 + 3
Connectors
2
4
+
-
-
+
+
+
Connectors
2: Control medium (open)
4: Control medium (close)
2: Control medium (open)
4: Control medium (close)

11.5 Setting the stroke limiter

The stroke limiter is used to reduce the
opening stroke by setting a preselected flow
rate.
For all actuator sizes the stroke is 1 mm /
turn.
Tools needed:
Actuator size 1:
Actuator size 2:
Actuator size 3:
Delivery condition of the stroke limiter:
The stroke limiter is fully open i.e. the stroke
limiter is inactive.
Procedure
1. Remove transparent cap: Either push a
2.5 mm screw driver into ready-made
grooves under the transparent cap
and carefully pry the transparent cap
upwards
or pull it up manually.
39 / 48
Socket wrench size 8
Socket wrench size 9
Socket wrench size 10
C60