11 Commissioning

+ = available
– = not available

10.2 Connecting the control medium

The product has 2 control medium connectors.
1. Use suitable connectors.
2. Connect the control medium lines tension-free and
without any bends or knots.
11 Commissioning
Corrosive chemicals!
▶ Risk of caustic burns
Wear appropriate protective gear.
Completely drain the plant.
Leakage
▶ Emission of dangerous materials.
Provide precautionary measures against exceeding the
maximum permitted pressures caused by pressure
surges (water hammer).
Use as end-of-line valve!
▶ Damage to the GEMÜ product.
When using the GEMÜ product as an
end-of-line valve, a mating flange must
be fitted.
Cleaning agent
▶ Damage to the GEMÜ product.
The plant operator is responsible for selecting the clean-
ing material and performing the procedure.
1. Check the tightness and the function of the product (close
and reopen the product).
2. Flush the piping system of new plant and following repair
work (the product must be fully open).
ð Harmful foreign matter has been removed.
ð The product is ready for use.
3. Commission the product.
4. Commissioning of actuators in accordance with the en-
closed instructions.
GEMÜ R690
WARNING
CAUTION
CAUTION
CAUTION

12 Operation

Operate the product according to the control function (see
also chapter "Pneumatic connections").

12.1 Control function 1

In its resting position, the product is closed by spring force.
1. Activate the actuator via control medium connector 2.
ð The product opens.
2. Vent the actuator via control medium connector 2.
ð The product closes.

12.2 Control function 2

In its resting position the product is opened by spring force.
1. Activate the actuator via control medium connector 4.
ð The product closes.
2. Vent the actuator via control medium connector 4.
ð The product opens.

12.3 Control function 3

In its resting position the product has no defined normal posi-
tion.
1. Activate the actuator via control medium connector 2.
ð The product opens.
2. Activate the actuator via control medium connector 4.
ð The product closes.